background image

Operating instructions

W3G630-KE55-51

Translation of the original operating instructions

1.11 Storage

;

Store the device, partially or fully assembled, in a dry place,
protected against the weather and free from vibration, in the original
packaging in a clean environment.

;

Protect the device against environmental effects and dirt until final
installation.

;

We recommend storing the device for no longer than one year in
order to guarantee trouble-free operation and the longest possible
service life.

;

Even devices explicitly intended for outdoor use are to be stored as
described prior to commissioning.

;

Maintain the storage temperature, see
Chapter 3.6 Transport and storage conditions.

2. INTENDED USE

The device is exclusively designed as a built-in device for conveying
air according to its technical data.
Any other usage above and beyond this does not conform with the
intended purpose and constitutes misuse of the device.
Customer equipment must be capable of withstanding the mechanical
and thermal stresses that can arise from this product. This applies for the
entire service life of the equipment in which this product is installed.

Intended use also includes

Using the device only in power systems with grounded neutral (TN/
TT power systems).

The device is to be used in networks with network quality
characteristics as per EN 50160.

Using the device only in stationary systems.

Performing all maintenance work.

Conveying air at an ambient air pressure between 800 mbar and
1050 mbar.

Using the device within the permitted ambient temperature range; see
Chapter 3.6 Transport and storage conditions and
Chapter 3.2 Nominal data.

Operating the device with all protective devices.

Following the operating instructions.

Improper use

In particular, operating the device in the following ways is prohibited and
could be hazardous:

Operating the device in an unbalanced state, e.g. due to dirt deposits
or ice formation.

Resonant operation, operation with severe vibration. This also
includes vibration transmitted to the fan from the customer installation.

Operation in medical equipment with a life-sustaining or life-support
function.

Conveying solids in the flow medium.

Painting the device

Connections (e.g. screws) coming loose during operation.

Conveying air that contains abrasive particles.

Conveying highly corrosive air, e.g. salt spray. Exception: devices
designed for salt spray and correspondingly protected.

Conveying air with high dust content, e.g. suctioning off sawdust.

Operating the device close to flammable materials or components.

Operating the device in an explosive atmosphere.

Using the device as a safety component or to perform safety-related
functions.

Operation with completely or partially disassembled or manipulated
protective devices.

In addition, all applications not listed among the intended uses.

Item no. 55309-5-9970 · ENU · Change 218409 · Approved 2020-10-06 · Page 3 / 14

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W3G630-KE55-51

Страница 1: ...install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be ass...

Страница 2: ...g in conjunction with open and closed loop control devices If impermissible radiation levels occur following installation appropriate shielding measures have to be taken by the user NOTE Electrical or...

Страница 3: ...ork Conveying air at an ambient air pressure between 800 mbar and 1050 mbar Using the device within the permitted ambient temperature range see Chapter 3 6 Transport and storage conditions and Chapter...

Страница 4: ...mm 1 Airflow direction V 2 Cable PVC AWG18 6x crimped ferrules 3 Cable PVC AWG22 5x crimped ferrules 4 Mounting holes for FlowGrid Item no 55309 5 9970 ENU Change 218409 Approved 2020 10 06 Page 4 14...

Страница 5: ...ort struts only in X position as illustrated or rotor on bottom 2 For horizontal shaft installation position the cable exit must be at the bottom right Item no 55309 5 9970 ENU Change 218409 Approved...

Страница 6: ...Technical description Weight 18 2 kg Size 630 mm Motor size 112 Rotor surface Painted black Electronics housing material Die cast aluminum painted black Blade material Press fitted sheet steel blank...

Страница 7: ...to prevent damage to the fan housing NOTE The heating tape has only basic insulation The heating tape may only be used with a closed fan housing cover to prevent heat losses and contact with live part...

Страница 8: ...rque recommended by ebm papst must be checked in the application concerned 4 2 Electrical connection DANGER Voltage on the device Electric shock Always connect a protective earth first Check the prote...

Страница 9: ...current devices cannot provide personal safety while operating the device When the device power supply is switched on pulsed charging currents from the capacitors in the integrated EMC filter can lea...

Страница 10: ...250 VAC 2 A AC1 min 10 mA reinforced insulation on supply side and basic insulation on control interface side 2 8 0 10V yellow Analog input set value 0 10 V Ri 100 k adjustable curve SELV 2 10 RSB br...

Страница 11: ...ranges with excessively high vibration levels and possibly resonant frequencies must be determined in the course of fan commissioning Either run through the resonant range as quickly as possible with...

Страница 12: ...y Device restarts automatically without warning Faulty connection Isolate from supply correct connection see connection diagram Broken motor winding Replace device Thermal overload protector activated...

Страница 13: ...onths Open holes Welds for crack formation Visual inspection At least every 6 months Replace device Abnormal bearing noise acoustic At least every 6 months Replace device 6 3 Disposal For ebm papst en...

Страница 14: ...r internal wiring Electrolytic capacitors Dispose of electronic components employing the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 553...

Отзывы: