Operating instructions

W3G630-GM07-H1

Translation of the original operating instructions

NOTE
Tightness and strain relief depend on the cable used.

→ The user must check this.

4.3.2 Connecting cables with terminals

WARNING
Terminals and connections have voltage even with a
unit that is shut off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

;

Remove the cap from the screwed cable gland.

Remove the cap only in those places where cables are inserted.

;

Insert the line(s) (not included in the standard scope of delivery) into
the terminal box.

;

First connect the "PE" (protective earth) connection.

;

Connect the lines to the corresponding terminals.

Use a screwdriver to do so.
During the connection work, ensure that no cables splice off.

;

Seal the terminal box.

4.3.3 Cable routing

No water may penetrate along the cable in the direction of the cable gland.

NOTE
Damage caused by moisture penetration.

Moisture can penetrate into the terminal box if water is
constantly present at the cable glands.
→ To prevent the constant accumulation of water at the cable

glands, the cable should be routed in a U-shaped loop
(siphon) wherever possible.

→ If this is not possible, a drip edge can be produced by

fitting a cable tie directly in front of the cable gland for example.

Fans installed lying flat

Make sure that the cable is routed in the form of a loop (water trap).

Fig. 2: Fan installed lying flat, cable routed in a U-shaped loop.

Fans installed in upright position

When routing the cable, ensure that the screwed cable glands are
arranged at the bottom. The cables must always be routed downwards.

Fig. 3: Cable routing for fans installed upright.

4.4 Factory settings

Factory settings with which the device is pre-set by ebm-papst.

Control mode
parameter set 1

PWM controlling

Control mode
parameter set 2

PWM controlling

Fan / device adress

1

Max. PWM / %

100

Min. PWM / %

10

Save set value to
EEPROM

No

Set value control

Analogue (linear)

Control function
parameter set 1

Positive (heating)

Control function
parameter set 2

Positive (heating)

Item no. 53504-5-9970 · ENG · Revision 222314 · Release 2021-02-01 · Page 8 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W3G630-GM07-H1

Страница 1: ...vice to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it...

Страница 2: ...asures have to be taken by the user NOTE Electrical or electromagnetic interferences after integrating the device in installations on the customer s side Verify that the entire setup is EMC compliant...

Страница 3: ...lowing ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibrations These also inclu...

Страница 4: ...d seal Cable diameter min 4 mm max 10 mm tightening torque 1 8 0 3 Nm 3 Cable diameter min 6 mm max 10 mm tightening torque 1 8 0 3 Nm use the provided seal Cable diameter min 4 mm max 7 mm tightening...

Страница 5: ...ardised measurement configuration 3 4 Technical features Mass 20 4 kg Size 630 mm Motor size 84 Surface of rotor Coated in black Material of terminal box PP plastic Material of electronics housing Die...

Страница 6: ...vice from its packaging only touching the wall ring Make sure to avoid any shock Wear safety shoes and cut resistant safety gloves CAUTION Heavy load when taking out the device Bodily harm e g back in...

Страница 7: ...uctor by way of the extra protective earth terminal provided on the device The protective earth terminal is located on the housing and provided with a protective earth symbol and a hole 4 2 2 Idle cur...

Страница 8: ...ands To prevent the constant accumulation of water at the cable glands the cable should be routed in a U shaped loop siphon wherever possible If this is not possible a drip edge can be produced by fit...

Страница 9: ...ommon connection contact rating 250 VAC 2 A AC1 min 10 mA basic insulation on mains side and reinforced insulation on control interface side 8 GND Signal ground for control interface SELV 9 RSA RS 485...

Страница 10: ...ice via the control input Do not switch the motor e g in cyclic operation on and off via power supply Switching off the device for maintenance work Switch off the device via the control input Do not s...

Страница 11: ...e device during cleaning Malfunction possible Do not use a high pressure cleaner to clean the device Do not use any acid alkali or solvent based cleaning agents Do not use any pointed or sharp edged o...

Страница 12: ...bled into suitable components for disposal employing standard procedures for motors WARNING Heavy parts of the product may drop off Some of the product components are heavy These components could drop...

Отзывы: