4.4 Connection diagram
Drawing preliminary!
No.
Conn.
Designation
Color
Function/assignment
1
1,2
PE
green/
yellow
Protective earth
1
3
N
blue
Power supply, neutral conductor, 50/60 Hz
1
4
L
black
Power supply, phase, 50/60 Hz
1
5
COM
white 1
Floating status contact, break for failure (2 A, max. 250 VAC, min. 10 mA, AC1)
1
6
NC
white 2
Floating status contact, break for failure
2
8
0 - 10 V
yellow
Control input, set value 0-10 VDC, impedance 100 kOhm, SELV
2
11
10 VDC
red
Voltage output 10 VDC (±3%), max. 10 mA, power supply for external devices (e.g.
potentiometers), SELV
2
12
GND
blue
Reference ground for control interface, SELV