Operating instructions
W3G500-DM56-35
Translation of the original operating instructions
4.5 Connection diagram
Drawing preliminary!
No.
Conn.
Designation
Function/assignment
PE
PE
Protective earth
KL1
N
Supply 50/60 Hz, neutral conductor
KL1
L
Supply 50/60 Hz, phase
KL2
COM
Alarm relay, common (2 A, 250 VAC, AC1)
KL2
NC
Alarm relay, break for failure
KL2
NO
Alarm relay, make for failure
KL3
+10 V
Supply for external potentiometer, 10 VDC (+10%) @ 10 mA
KL3
+20 V
Supply for external sensor, 20 VDC (±20%) @ 50 mA
KL3
0-10 V/PWM
Control / current sensor value input
KL3
0-10 V/PWM
Control / current sensor value input (impedance 100 kΩ)
KL3
4-20 mA
Control / current sensor value input
KL3
GND
GND
KL3
GND
GND
KL3
OUT
Master output 0-10 V, max. 3 mA
KL3
RSA
RS485 interface for ebmBUS, RSA
KL3
RSA
RS485 interface for ebmBUS, RSA
KL3
RSB
RS485 interface for ebmBUS, RSB
KL3
RSB
RS485 interface for ebmBUS, RSB
Item no. 52188-5-9970 · ENU · Change 88834 · Approved 2016-05-03 · Page 9 / 12