3.2 Nominal data

Motor

M3G084-FA

Phase

3~

Nominal voltage / VAC

400

Nominal voltage
range / VAC

380 .. 480

Frequency / Hz

50/60

Method of obtaining
data

ml

Speed (rpm) / min

-1

1500

Power consumption / W

500

Current draw / A

0.83

Max. back pressure / Pa

150

Min. ambient
temperature / °C

-40

Max. ambient
temperature / °C

60

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Data according to Commission Regulation (EU) 327/
2011

Actual

Req. 2015

01 Overall efficiency η

es

/ %

37.8

31.9

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

45.9

40

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
product's rating label.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart
· HRA 590344
D-74673 Mulfingen

08 Type

W3G450-CL12-N1

09 Power consumption P

ed

/ kW

0.52

09 Air flow q

v

/ m³/h

4755

09 Pressure increase total p

sf

/

Pa

135

10 Speed (rpm) n / min

-1

1500

11 Specific ratio

*

1.00

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data obtained at optimum efficiency level. The ErP data is determined using a motor-impeller

combination in a standardized measurement setup.

3.4 Technical description

Weight

12.7 kg

Size

450 mm

Motor size

84

Rotor surface

Painted black

Electronics housing
material

Die-cast aluminum, painted black

Impeller material

PA plastic, sheet-metal plate painted black

Support ring material

Stainless steel

Fan housing material

Sheet steel, galvanized and coated with
black plastic (RAL 9005)

Number of blades

5

Airflow direction

A

Direction of rotation

Clockwise, viewed toward rotor

Degree of protection

IP55

Insulation class

"F"

Moisture (F) /
Environmental (H)
protection class

H3

Installation position

Shaft horizontal or rotor on top; rotor on
bottom on request

Condensation
drainage holes

None

Mode

S1

Motor bearing

Ball bearing; (sealed)

Technical features

- Output 10 VDC, max. 10 mA
- Alarm relay
- Integrated PID controller
- Run monitoring
- Power limiter
- Motor current limitation
- Emergency operation
- PFC, passive
- RS-485 MODBUS-RTU
- Soft start
- EEPROM write cycles: 100,000
maximum
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Overvoltage detection
- Thermal overload protection for
electronics/motor
- Line undervoltage / phase failure
detection

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Motor protection

Thermal overload protector (TOP)
internally connected

with cable

Lateral

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 15085-1, CPC3: 2007; EN 45545-2,
HL3: 2013 + A1:2015; EN 50155: 2008;
EN 61373, Cat. 1B: 2010; CE

Approval

EAC

Item no. 56615-5-9970 · ENU · Change 213523 · Approved 2020-03-10 · Page 5 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W3G450-CL12-N1

Страница 1: ...specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associate...

Страница 2: ...appropriate shielding measures have to be taken by the user NOTE Electrical or electromagnetic interference after installing the device in customer equipment Verify that the entire setup is EMC compl...

Страница 3: ...se In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operatio...

Страница 4: ...2 Cable halogen free railway application EN 45545 4G 1 5 mm 4x wire end ferrule 3 Cable halogen free railway application EN 45545 7X 0 5 mm 7x wire end ferrule Item no 56615 5 9970 ENU Change 213523...

Страница 5: ...d using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 12 7 kg Size 450 mm Motor size 84 Rotor surface Painted black Electronics housing material Die...

Страница 6: ...ngement It is the responsibility of the installation engineer or operator owner of the device to ensure if necessary after consultation with the network operator that this device is only connected to...

Страница 7: ...VAC 25 A 25 A C25A 4 0 12 AWG American Wire Gauge 4 2 3 Reactive currents Because of the EMC filter integrated for compliance with EMC limits interference emission and immunity to interference reactiv...

Страница 8: ...s made for the device by ebm papst Mode parameter set 1 PWM control Mode parameter set 2 PWM control Fan device address 01 Max PWM 100 Min PWM 10 Save set value to EEPROM No Set value requirement Anal...

Страница 9: ...us relay floating status contact break for failure contact rating 250 VAC 30 VDC 5 A minimum contact separation 1 mA 5 VDC reinforced insulation on supply side basic insulation on control interface si...

Страница 10: ...ower supply When disconnecting be sure to disconnect the ground connection last 5 INTEGRATED PROTECTIVE FEATURES The integrated protective functions cause the motor to switch off automatically in the...

Страница 11: ...6 1 Cleaning To ensure a long service life check the fans regularly for proper operation and soiling The frequency of checking is to be adapted accordingly depending on the degree of soiling DANGER R...

Страница 12: ...regard to the disposal of products or waste occurring in the various phases of the life cycle The corresponding disposal standards are also to be heeded 6 3 2 Disassembly Disassembly of the product mu...

Отзывы: