Operating instructions

W3G350-JN01-30

Translation of the original operating instructions

Information on surface quality

The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may change during the production period.
This has no effect on strength, dimensional stability and dimensional
accuracy.
The color pigments in the paints used perceptibly react to UV light over
the course of time. This does not however in any way affect the
technical properties of the products. The product is to be protected against
UV radiation to prevent the formation of patches and fading. Changes in
color are not a reason for complaint and are not covered by the warranty.

3.5 Mounting data

For screw clearance, see Chapter 3.1 Product drawing

;

Secure the screws against unintentional loosening (e.g. use self-
locking screws).

Strength class of
screws

8.8

Any further mounting data required can be taken from the product
drawing or Section Chapter 4.1 Mechanical connection.

3.6 Transport and storage conditions

Max. permitted
ambient temp. for
motor (transport/
storage)

+ 70 °C

Min. permitted
ambient temp. for
motor (transport/
storage)

- 40 °C

3.7 Accessories

3.7.1 AxiCool heating tape

A heating tape that can be installed in the fan housing is available for the
AxiCool fans. To prevent ice formation, ebm-papst recommends the use
of a heating tape for all applications below 0 °C. The heating tape
designed for the AxiCool fan housing is available from ebm-papst under
the following item numbers.

Fan size

Item no.

300 mm

00300-2-7680

350 mm

00350-2-7680

450 mm

00450-2-7680

During assembly, comply with the installation instructions included with
each ebm-papst heating tape.
ebm-papst assumes no liability when heating tapes from other
manufacturers are used. Note the maximum permitted temperature of
+60 ± 5 °C for the heating tape to prevent damage to the wall ring.

4. CONNECTION AND STARTUP

4.1 Mechanical connection

CAUTION
Cutting and crushing hazard when removing device
from packaging

Blades can bend
→ Carefully remove the device from its packaging, by the fan

housing. Strictly avoid shocks.

→ Wear safety shoes and cut-resistant safety gloves.

NOTE
Damage to the device from vibration

Bearing damage, shorter service life
→ The fan must not be subjected to force or excessive vibration

from sections of the installation.

→ If the fan is connected to air ducts, the connection should

be isolated from vibration, e.g. using compensators or similar
elements.

→ Ensure stress-free attachment of the fan to the

substructure.

;

Check the device for transport damage. Damaged devices are not to
be installed.

;

Install the undamaged device in accordance with your application.

CAUTION
Possible damage to the device

If the device slips during installation, serious damage can result.
→ Ensure that the device is securely positioned at its place of

installation until all fastening screws have been tightened.

The fan must not be strained on fastening.

4.2 Electrical connection

DANGER
Voltage on the device

Electric shock
→ Always connect a protective earth first.
→ Check the protective earth.

DANGER
Faulty insulation

Risk of fatal injury from electric shock
→ Use only cables that meet the specified installation

regulations for voltage, current, insulation material, capacity,
etc.

→ Route cables so that they cannot be touched by any

rotating parts.

DANGER
Electrical charge (>50 µC) between phase conductor and
protective earth connection after switching off supply
with multiple devices connected in parallel.

Electric shock, risk of injury
→ Ensure sufficient protection against accidental contact.

Before working on the electrical hookup, short the supply
and PE connections.

Item no. 52107-5-9970 · ENU · Change 208645 · Approved 2019-10-25 · Page 6 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W3G350-JN01-30

Страница 1: ...l staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The s...

Страница 2: ...y that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accide...

Страница 3: ...prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration...

Страница 4: ...ng All dimensions in mm 1 Direction of air flow V 2 Cable PVC 4G 0 5 mm 4x crimped splices 3 Mounting dimensions Item no 52107 5 9970 ENU Change 208645 Approved 2019 10 25 Page 4 11 ebm papst Mulfinge...

Страница 5: ...ata obtained at optimum efficiency level The ErP data is determined using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 4 kg Size 350 mm Motor size...

Страница 6: ...e heating tape to prevent damage to the wall ring 4 CONNECTION AND STARTUP 4 1 Mechanical connection CAUTION Cutting and crushing hazard when removing device from packaging Blades can bend Carefully r...

Страница 7: ...onnect an additional protective earth conductor by way of the extra protective earth terminal provided on the device 4 2 2 Reactive currents Because of the EMC filter integrated for compliance with EM...

Страница 8: ...230 VAC 50 60 Hz see nameplate for voltage range CON 11 N blue Neutral conductor CON 12 PE green yellow Protective earth CON 70 SL brown Speed selection switch open speed 1 switch closed speed 2 Item...

Страница 9: ...d connection last 5 INTEGRATED PROTECTIVE FEATURES The integrated protective functions cause the motor to switch off automatically in the event of the faults described in the table Fault Safety featur...

Страница 10: ...rings is designed for a service life of 40 000 hours If bearing replacement is necessary after that period contact ebm papst Adapt the maintenance intervals to the actual level of dust exposure 6 2 Sa...

Страница 11: ...num Non ferrous metal e g motor windings Plastics particularly with brominated flame retardants in accordance with marking Insulating materials Cables and wires Electronic scrap e g circuit boards Onl...