background image

Operating instructions

W3G350-CG03-32

Translation of the original operating instructions

WARNING
Live terminals and connections even with device
switched off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

CAUTION
In the event of a fault, the rotor and the impeller will be
energized

The rotor and the impeller have basic insulation.
→ Do not touch the rotor and impeller once installed.

CAUTION
If control voltage or a stored speed set value is applied,
the motor will restart automatically, e.g. after a power
failure.

Risk of injury
→ Keep out of the device’s danger zone.
→ When working on the device, switch off the line voltage

and ensure that it cannot be switched back on.

→ Wait until the device comes to a stop.
→ After working on the device, remove any tools or other

objects from the device.

1.5 Safety and protective features

DANGER
Protective device missing and protective device not
functioning

Without a protective device there is a risk of serious injury, for
instance when reaching into the device during operation.
→ Operate the device only with a fixed protective device and

guard grille.

→ The fixed protective device must be able to withstand the

kinetic energy of a fan blade that becomes detached at
maximum speed. There must not be any gaps which it is
possible to reach into with the fingers, for example.

→ The device is a built-in component. As the operator, you

are responsible for ensuring that the device is secured
adequately.

→ Stop the device immediately if you notice a missing or

ineffective protective device.

1.6 Electromagnetic radiation

Interference from electromagnetic radiation is possible, e.g. in conjunction
with open- and closed-loop control devices.
If impermissible radiation levels occur following installation, appropriate
shielding measures have to be taken by the user.

NOTE
Electrical or electromagnetic interference after installing
the device in customer equipment.

→ Verify that the entire setup is EMC-compliant.

1.7 Mechanical movement

DANGER
Rotating device

Risk of injury to body parts coming into contact with the rotor or
the impeller.
→ Secure the device against accidental contact.
→ Before working on the system/machine, wait until all

parts have come to a standstill.

WARNING
Rotating device

Long hair and dangling items of clothing, jewelry and the like
can become entangled and be pulled into the device. Injuries
can result.
→ Do not wear any loose-fitting or dangling clothing or jewelry

while working on rotating parts.

→ Protect long hair with a cap.

1.8 Emissions

WARNING
Depending on the installation and operating conditions,
the sound pressure level may exceed 70 dB(A).

Risk of noise-induced hearing loss
→ Take appropriate technical safety measures.
→ Protect operating personnel with appropriate safety

equipment such as hearing protection.

→ Also observe the requirements of local agencies.

1.9 Hot surface

CAUTION
High temperature on electronics housing

Risk of burns
→ Ensure sufficient protection against accidental contact.

1.10 Transport

NOTE
Transporting the device

→ Transport the device in its original packaging only.

1.11 Storage

;

Store the device, partially or fully assembled, in a dry place,
protected against the weather and free from vibration, in the original
packaging in a clean environment.

;

Protect the device against environmental effects and dirt until final
installation.

;

We recommend storing the device for no longer than one year in
order to guarantee trouble-free operation and the longest possible
service life.

;

Even devices explicitly intended for outdoor use are to be stored as
described prior to commissioning.

;

Maintain the storage temperature, see
Chapter 3.5 Transport and storage conditions.

Item no. 51501-5-9970 · ENU · Change 202174 · Approved 2019-01-04 · Page 2 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W3G350-CG03-32

Страница 1: ...authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basi...

Страница 2: ...lectrical or electromagnetic interference after installing the device in customer equipment Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury...

Страница 3: ...ld be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the...

Страница 4: ...imensions in mm 1 Direction of air flow V 2 Cable PVC 3x AWG20 3x crimped splices 3 Cable PVC 4xAWG22 4x crimped splices Item no 51501 5 9970 ENU Change 202174 Approved 2019 01 04 Page 4 11 ebm papst...

Страница 5: ...CSA C22 2 No 77 CAN CSA E60730 1 With regard to cyclic speed loads note that the rotating parts of the device are designed for a maximum of one million load cycles If you have special questions consul...

Страница 6: ...cables Water ingress at the customer end of the cable can damage the device Make sure the end of the cable is connected in a dry environment Only connect the device to circuits that can be switched o...

Страница 7: ...nt LRA is equal to or less than the nominal current FLA 4 3 Connecting the cables The device has external leads First connect the PE protective earth Connect the cables according to your application W...

Страница 8: ...ve earth 1 GND blue GND connection for control interface 2 0 10V PWM yellow Control input 0 10 V or PWM electrically isolated 3 10 V max 1 1 mA red Voltage output 10 VDC 1 1 mA electrically isolated s...

Страница 9: ...nnecting be sure to disconnect the ground connection last 5 INTEGRATED PROTECTIVE FEATURES The integrated protective functions cause the motor to switch off automatically in the event of the faults de...

Страница 10: ...n accordance with ISO 14001 and rigorously implemented around the world on the basis of German standards Right from the development stage ecological design technical safety and health protection are f...

Страница 11: ...omponents employing the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 51501 5 9970 ENU Change 202174 Approved 2019 01 04 Page 11 11 ebm pa...

Отзывы: