4.2.1 Requirements
;
Check whether the information on the nameplate matches the
connection data.
;
Before connecting the device, make sure the power supply matches
the device voltage.
;
Only use cables designed for the current level indicated on the
nameplate.
For determining the cross-section, note the sizing criteria according
to EN 61800-5-1. The protective earth must have a cross-section
equal to or greater than that of the phase conductor.
We recommend the use of 105 °C cables. Ensure that the minimum
cable cross-section is at least
AWG 26 / 0.13 mm².
Operate the device with a safely isolated power supply.
4.3 Plug connection
4.3.1 Making supply connections
;
Check your connector's pin assignment.
;
Connect the built-in connector with the mating connector.
;
Ensure that the connector is properly engaged.