ebm-papst W2E200-HK86-01 Скачать руководство пользователя страница 9

Operating instructions

W2E200-HK86-01

Translation of the original operating instructions

Insufficient cooling

Improve cooling

If you have any other problems, contact ebm-papst.

5.1 Cleaning

To ensure a long service life, the fans have to be regularly checked for
proper operation and degree of soiling. The frequency of the checks is to
be adapted to the occurrence of soiling.

DANGER
Risk of injury from rotating fan.

→ Only clean when not in motion. Interrupt the power supply,

secure against renewed switch-on. Secure against start-up,
prevent air flow.

;

Dirt deposits on the motor housing could lead to overheating of the
motor.

;

Dirt on the impeller can cause vibration which would shorten the
service life of the fan.

;

Severe vibration could destroy the fan.

;

In such cases immediately switch off and clean the fan.

;

The preferred method of cleaning is dry cleaning, e.g. using
compressed air.

;

Use is never to be made of corrosive cleaning agents!

NOTE
Damage to the device during cleaning

Malfunction possible
→ Do not clean the device using a water jet or high-pressure

cleaner.

→ Do not use any acid, alkali or solvent-basedcleaning

agents.

→ Do not use any pointed or sharp-edged objects for cleaning

;

Completely remove any cleaning agents used.

;

Immediately switch off and replace the device if severe corrosion is
apparent at load-bearing or rotating parts.

;

Repairs to load-bearing or rotating parts are not permissible!

;

Operate the fan for 2 hours at maximum speed to permit the
evaporation of any water which may have ingressed.

;

If cleaning does not eliminate vibration, the fan may have to be re-
balanced. In such cases please contact ebm-papst.

;

The fan is provided with maintenance-free ball bearings. The lifetime
lubrication of the ball bearings is designed for a service life of 40,000
hours.

;

Please contact ebm-papst if bearing replacement is required after this
period.

;

Adapt the maintenance intervals to the dust pollution occurring.

5.2 Safety test

What has to
be tested?

How to test?

Frequency

Which
measure?

Check the
protective
casing against
accidental
contact for
damage and to
ensure that it is
intact

Visual inspection At least every

6 months

Repair or
replacement of
the device

Check the
device for
damage to
blades and
housing

Visual inspection At least every

6 months

Replacement of
the device

Mounting the
connection lines

Visual inspection At least every

6 months

Fasten

Mounting of
protective earth
connection

Visual inspection At least every

6 months

Fasten

Check the
insulation of the
wires for damage

Visual inspection At least every

6 months

Replace wires

Weld seams for
crack formation

Visual inspection At least every

6 months

Replace device

Abnormal
bearing noise

acoustic

At least every
6 months

Replace device

5.3 Disposal

For ebm-papst, environmental protection and resource preservation are
top priority corporate goals.
ebm-papst operates an environmental management system which is
certified in accordance with ISO 14001 and rigorously implemented
around the world on the basis of German standards.
Right from the development stage, ecological design, technical safety
and health protection are fixed criteria.
The following section contains recommendations for ecological disposal
of the product and its components.

5.3.1 Country-specific legal requirements

NOTE
Country-specific legal requirements

Always observe the applicable country-specific legal
regulations with regard to the disposal of products or waste
occurring in the various phases of the life cycle. The
corresponding disposal standards are also to be heeded.

5.3.2 Disassembly

Disassembly of the product must be performed or supervised by
qualified personnel with the appropriate technical knowledge.
The product is to be disassembled into suitable components for disposal
employing standard procedures for motors.

WARNING
Heavy parts of the product may drop off. Some of the
product components are heavy. These components
could drop off during disassembly.

This can result in fatal or serious injury and material damage.
→ Secure components before unfastening to stop them falling.

Item no. 11016-5-9970 · ENG · Revision 260800 · Release 2022-07-13 · Page 9 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W2E200-HK86-01

Страница 1: ...installed operated maintained and otherwise used by qualified trained and authorised technical staff Only authorised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device The loca...

Страница 2: ... 1 6 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair dangling items of clothing jewellery and similar items can become entangled and be pulled into the device Risk o...

Страница 3: ...e with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibrations These also include vibrations that are transmitted from the customer system to the fan Operation in medical equipment with a life sustaining or lifesaving function Moving solids content in flow medium Painting the device Connections e g screws coming loose during operation Moving air that contai...

Страница 4: ...Product drawing All measures have the unit mm 1 Direction of air flow V 2 For self tapping M5 screws Item no 11016 5 9970 ENG Revision 260800 Release 2022 07 13 Page 4 10 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 5: ...stomer Motor capacitor according to EN 60252 1 in safety protection class S0 Product conforming to standard EN 60335 1 Standard conformity UKCA Product conforming to standard CE Approval UL 507 VDE EAC CCC CSA C22 2 no 113 Use the device in accordance with its protection type Notes on surface quality The surfaces of the products conform to the generally applicable industrial standard The surface q...

Страница 6: ...t according to the type plate For determining the cross section follow the basic principles in accordance with EN 61800 5 1 The protective earth must have a cross section equal to or greater than the outer conductor cross section We recommend the use of 105 C cables Ensure that the minimum cable cross section is at least AWG26 0 13 mm Protective earth contact resistance as per EN 60335 Compliance ...

Страница 7: ...uctions 4 4 Connection screen U1 blue Z brown U2 black PE green yellow Item no 11016 5 9970 ENG Revision 260800 Release 2022 07 13 Page 7 10 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 8: ... MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perform any repairs on your device Return the device to ebm papst for repair or replacement WARNING Terminals and connections have voltage even with a unit that is shut off Electric shock Wait five minutes after disconnecting the voltage at all poles before opening the device CAUTION Electrical load on the capacitor after device is switched off Ele...

Страница 9: ...ccidental contact for damage and to ensure that it is intact Visual inspection At least every 6 months Repair or replacement of the device Check the device for damage to blades and housing Visual inspection At least every 6 months Replacement of the device Mounting the connection lines Visual inspection At least every 6 months Fasten Mounting of protective earth connection Visual inspection At lea...

Страница 10: ... external rotor motors from ebm papst Mulfingen GmbH Co KG Ferrite magnets can be disposed of in the same way as normal iron and steel Electrical insulating materials on the product in cables and wires are made of similar materials and are therefore to be treated in the same manner The materials concerned are as follows Miscellaneous insulators used in the terminal box Power lines Cables for inter...

Отзывы: