Operating instructions

S6E710-AR03-01

Translation of the original operating instructions

4.3.2 Connecting wires to terminals

;

Remove the cap from the cable gland.

Only remove caps where cables are fed in.

;

Route the wire(s) (not included in scope of delivery) into the terminal
box.

;

First connect the "PE" (protective earth).

;

Connect the wires to the corresponding terminals.

;

Connect the thermal overload protector (TOP).

Use a screwdriver to do so.
When connecting, ensure that no wire ends fan out.
The terminal strip is equipped with a penetration guard.

;

Insert the leads until they meet resistance.

;

Seal the terminal box.

4.3.3 Cable routing

Water must be prevented from reaching the cable gland along the cable.

NOTE
Damage caused by moisture penetration.

Moisture can penetrate into the terminal box if water is
constantly present at the cable glands.
→ To prevent the constant accumulation of water at the cable

glands, the cable should be routed in a U-shaped loop
wherever possible.

→ If this is not possible, a drip edge can be produced by

fitting a cable tie directly in front of the cable gland for example.

Fans installed lying flat

Make sure the cable is routed in a U-shaped loop.

Fig. 2: Fan installed lying flat, cable routed in a U-shaped loop.

Fans installed upright

When routing the cable, make sure that the cable glands are located at
the bottom. The cables must always be routed downward.

Fig. 3: Cable routing for fans installed upright.

4.3.4 Motor protection

CAUTION
Voltage

The device is a built-in component and has no disconnecting
switch.
→ Connect the device to a suitable tripping unit.
→ Only connect the device to circuits that can be switched

off with an all-pole disconnection switch.

→ When working on the device, secure the system/

machine in which the device is installed so as to prevent it
from being switched back on.

NOTE
Lack of motor protection

Without motor protection, the motor can overheat and suffer
damage.
→ Connect the thermal overload protector installed in the

winding.

The motors are equipped with thermal overload protectors to protect the
devices.
Check to make sure that the thermal overload protector is correctly
connected before each operation.
Failure to connect the thermal overload protector correctly will
invalidate your warranty claim.

Item no. 10160-5-9970 · ENU · Change 98149 · Approved 2018-07-24 · Page 8 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание S6E710-AR03-01

Страница 1: ...authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic...

Страница 2: ...step on the guard grill or subject the guard grill to load Do not place any objects on the guard grill There must be sufficient space around the fan to be able to get past the fan 1 6 Mechanical move...

Страница 3: ...hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fan...

Страница 4: ...ns in mm 1 Direction of air flow V 2 Tightening torque 1 5 0 2 Nm 3 Cable diameter min 6 mm max 12 mm tightening torque 2 0 3 Nm Item no 10160 5 9970 ENU Change 98149 Approved 2018 07 24 Page 4 12 ebm...

Страница 5: ...eclaration Specific ratio 1 pfs 100 000 Pa Data obtained at optimum efficiency level The ErP data is determined using a motor impeller combination in a standardized measurement setup 3 4 Technical des...

Страница 6: ...gether to remove the device from its packaging CAUTION The blades of the impeller could be damaged Carefully set down the fan on a soft surface Make sure the blades are not subjected to load Following...

Страница 7: ...ccording to EN 61800 5 1 Compliance with the resistance specifications according to EN 61800 5 1 for the protective earth connection circuit must be verified in the end application Depending on the in...

Страница 8: ...e cable is routed in a U shaped loop Fig 2 Fan installed lying flat cable routed in a U shaped loop Fans installed upright When routing the cable make sure that the cable glands are located at the bot...

Страница 9: ...4 4 Connection diagram L U1 blue Z brown N U2 black PE green yellow TOP gray Item no 10160 5 9970 ENU Change 98149 Approved 2018 07 24 Page 9 12 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mul...

Страница 10: ...tire speed control range Severe vibration can arise for instance from inexpert handling transportation damage and resultant imbalance or be caused by component or structural resonance Speed ranges wit...

Страница 11: ...e Abnormal bearing noise acoustic At least every 6 months Replace device 5 3 Disposal For ebm papst environmental protection and resource preservation are top priority corporate goals ebm papst operat...

Страница 12: ...The materials concerned are as follows Miscellaneous insulators used in the terminal box Power cables Cables for internal wiring Electrolytic capacitors Dispose of electronic components employing the...

Отзывы: