background image

Operating instructions

S6D500-AJ03-01

Translation of the original operating instructions

3.2 Nominal data

Motor

M6D110-EF

Phase

3~

3~

3~

3~

Nominal voltage / VAC

400

400

400

400

Wiring

Δ

Y

Δ

Y

Frequency / Hz

50

50

60

60

Method of obtaining
data

ml

ml

ml

ml

Valid for approval/
standard

-

-

-

-

Speed (rpm) / min

-1

930

800

1050

800

Power consumption / W

270

190

380

250

Current draw / A

0.69

0.4

0.75

0.43

Max. back pressure / Pa

75

55

90

55

Min. ambient
temperature / °C

-40

-40

-40

-40

Max. ambient
temperature / °C

65

65

65

65

Starting current / A

2.5

2.3

Max. safe operating
speed (rpm) /
min

-1

1920
@ 55 °C

1920
@ 55 °C

1920
@ 55 °C

1920
@ 55 °C

Phase

3~

3~

Nominal voltage / VAC

480

480

Wiring

Δ

Y

Frequency / Hz

60

60

Method of obtaining
data

ml

ml

Valid for approval/
standard

-

-

Speed (rpm) / min

-1

1100

910

Power consumption / W

415

295

Current draw / A

0.78

0.45

Max. back pressure / Pa

100

70

Min. ambient
temperature / °C

-40

-40

Max. ambient
temperature / °C

65

65

Starting current / A

2.8

Max. safe operating
speed (rpm) /
min

-1

1920
@ 55 °C

1920
@ 55 °C

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Technical description

Weight

10.7 kg

Fan size

500 mm

Rotor surface

Painted black

Terminal box material

PP plastic

Blade material

Press-fitted sheet steel blank, sprayed
with PP plastic

Guard grille material

Steel, coated with black plastic (RAL
9005)

Number of blades

5

Airflow direction

"V"

Direction of rotation

Counterclockwise, viewed toward rotor

Degree of protection

IP54

Insulation class

"F"

Moisture (F) /
Environmental (H)
protection class

F4-1

Installation position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensation
drainage holes

On rotor side

Mode

S1

Motor bearing

Ball bearing

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Electrical hookup

Via terminal box

Motor protection

Thermal overload protector (TOP) with
basic insulation

with cable

Axial

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 61800-5-1

Approval

EAC; VDE

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

3.4 Mounting data

;

Secure the screws against unintentional loosening (e.g. use self-
locking screws).

Strength class of
screws

8.8

Any further mounting data required can be taken from the product drawing.

3.5 Transport and storage conditions

;

Use the device in accordance with its degree of protection.

Max. permitted
ambient temp. for
motor (transport/
storage)

+ 80 °C

Min. permitted
ambient temp. for
motor (transport/
storage)

- 40 °C

Item no. 10069-5-9970 · ENU · Change 89187 · Approved 2016-04-15 · Page 5 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание S6D500-AJ03-01

Страница 1: ...packed installed operated maintained and otherwise used by suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test...

Страница 2: ...he impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair and dangling items of clo...

Страница 3: ...g instructions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice fo...

Страница 4: ...ns in mm 1 Direction of air flow V 2 Tightening torque 1 5 0 2 Nm 3 Cable diameter min 6 mm max 12 mm tightening torque 2 0 3 Nm Item no 10069 5 9970 ENU Change 89187 Approved 2016 04 15 Page 4 10 ebm...

Страница 5: ...plastic RAL 9005 Number of blades 5 Airflow direction V Direction of rotation Counterclockwise viewed toward rotor Degree of protection IP54 Insulation class F Moisture F Environmental H protection cl...

Страница 6: ...e to circuits that can be switched off with an all pole disconnection switch 4 2 1 Requirements Check whether the data on the nameplate match the connection data Before connecting the device make sure...

Страница 7: ...nstalled lying flat Make sure the cable is routed in a U shaped loop Fig 2 Fan installed lying flat cable routed in a U shaped loop Fans installed upright When routing the cable make sure that the cab...

Страница 8: ...tion Y Star connection L1 V1 blue L2 U1 black L3 W1 brown W2 yellow U2 green V2 white TOP 2x gray PE green yellow Item no 10069 5 9970 ENU Change 89187 Approved 2016 04 15 Page 8 10 ebm papst Mulfinge...

Страница 9: ...ne s main switch When disconnecting be sure to disconnect the ground connection last 5 MAINTENANCE MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perform any repairs on your device Send the device t...

Страница 10: ...requirements Always observe the applicable country specific legal regulations with regard to the disposal of products or waste occurring in the various phases of the life cycle The corresponding disp...

Отзывы: