3.2 Nominal data

Motor

M4E068-EC

Phase

1~

1~

Nominal voltage / VAC

230

230

Frequency / Hz

50

60

Valid for approval/
standard

CE

CE

Speed (rpm) / min

-1

1335

1550

Power consumption / W

150

175

Current draw / A

0.67

0.78

Capacitor / µF

4

4

Capacitor voltage / VDB

400

400

Min. ambient
temperature / °C

-25

-25

Max. ambient
temperature / °C

-

-

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Technical description

Weight

4.4 kg

Size

350 mm

Motor size

68

Rotor surface

Painted black

Terminal box material

PC/ABS plastic

Blade material

Press-fitted sheet steel blank, sprayed
with PA plastic

Guard grille material

Steel, phosphated and coated with black
plastic

Number of blades

7

Airflow direction

V

Direction of rotation

Counterclockwise, viewed toward rotor

Degree of protection

IP44; installation- and position-dependent
as per EN 60034-5

Insulation class

"F"

Moisture (F) /
Environmental (H)
protection class

F2-2; H1+

Installation position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensation
drainage holes

On rotor side

Mode

S1

Motor bearing

Ball bearing

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

< 0.75 mA

Electrical hookup

Terminal box; Via terminal box, capacitor
integrated and connected

Motor protection

Thermal overload protector (TOP)
internally connected

with cable

Axial

Protection class

I (with customer connection of protective
earth)

Motor capacitor
according to EN 60252-
1 in safety protection
class

S0

Conformity with
standards

EN 60335-1; CE

Approval

CCC

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

;

Use the device in accordance with its degree of protection.

Information on surface quality

The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may change during the production period.
This has no effect on strength, dimensional stability and dimensional
accuracy.
The color pigments in the paints used perceptibly react to UV light over
the course of time. This does not however in any way affect the
technical properties of the products. The product is to be protected against
UV radiation to prevent the formation of patches and fading. Changes in
color are not a reason for complaint and are not covered by the warranty.

3.4 Mounting data

;

Secure the screws against unintentional loosening (e.g. use self-
locking screws).

Strength class of
screws

8.8

Any further mounting data required can be taken from the product
drawing or Section Chapter 4.1 Mechanical connection.

3.5 Transport and storage conditions

Max. permitted
ambient temp. for
motor (transport/
storage)

+ 80 °C

Min. permitted
ambient temp. for
motor (transport/
storage)

- 40 °C

Item no. 11607-5-9970 · ENU · Change 98705 · Approved 2018-04-27 · Page 5 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание S4E350-AG06-28

Страница 1: ...y suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation in the final product The locally applicable industrial safety...

Страница 2: ... rotor or the impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become entangled and be pulled into the device Injuries can result Do not wear any loose fitting or dangling clothing or jewelry while working on rotating par...

Страница 3: ...e device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fan from the customer installation Opening the terminal box during operation Conveying air that contains abrasive particles Conveying highly corros...

Страница 4: ...ection of air flow V 2 Tightening torque 0 7 0 2 Nm 3 Shown without terminal box cover 4 Cable diameter max 7 5 mm tightening torque 1 3 0 2 Nm Item no 11607 5 9970 ENU Change 98705 Approved 2018 04 27 Page 4 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 5: ...lass I with customer connection of protective earth Motor capacitor according to EN 60252 1 in safety protection class S0 Conformity with standards EN 60335 1 CE Approval CCC With regard to cyclic speed loads note that the rotating parts of the device are designed for a maximum of one million load cycles If you have special questions consult ebm papst for support Use the device in accordance with ...

Страница 6: ... cable is connected in a dry environment Only connect the device to circuits that can be switched off with an all pole disconnection switch 4 2 1 Requirements Check whether the information on the nameplate matches the connection data If the motor run capacitor was not installed by ebm papst check whether the information on the motor run capacitor matches the information on the nameplate Before con...

Страница 7: ...hey meet resistance Seal the terminal box 4 3 3 Cable routing Water must be prevented from reaching the cable gland along the cable NOTE Damage caused by moisture penetration Moisture can penetrate into the terminal box if water is constantly present at the cable glands To prevent the constant accumulation of water at the cable glands the cable should be routed in a U shaped loop wherever possible...

Страница 8: ...ctions 4 4 Connection diagram L U1 blue Z brown N U2 black PE green yellow Item no 11607 5 9970 ENU Change 98705 Approved 2018 04 27 Page 8 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 9: ...ise for instance from inexpert handling transportation damage and resultant imbalance or be caused by component or structural resonance Speed ranges with excessively high vibration levels and possibly resonant frequencies must be determined in the course of fan commissioning Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with excess...

Страница 10: ...rld on the basis of German standards Right from the development stage ecological design technical safety and health protection are fixed criteria The following section contains recommendations for ecological disposal of the product and its components 5 3 1 Country specific legal requirements NOTE Country specific legal requirements Always observe the applicable country specific legal regulations w...

Страница 11: ...employing the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 11607 5 9970 ENU Change 98705 Approved 2018 04 27 Page 11 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Отзывы: