Operating instructions
S3G710-AO85-21
Translation of the original operating instructions
4.6 Checking connections
;
Ensure isolation from supply (all phases).
;
Make sure a restart is impossible
;
Check the cables for proper fit.
4.7 Switching on the device
The device may only be switched on if it has been installed properly and
in accordance with its intended use, including the required safety
mechanisms and professional electrical hookup. This also applies for
devices which have already been equipped with plugs and terminals or
similar connectors by the customer.
WARNING
Hot motor housing
Risk of fire
→ Ensure that no combustible or flammable materials are
located close to the fan.
;
Before switching on, check the device for visible external damage
and make sure the protective devices are functional.
;
Check the fan's air flow paths for foreign matter and remove any
foreign matter found.
;
Apply the nominal supply voltage.
;
Start the device by changing the input signal.
4.8 Switching off the device
Switching off the device during operation:
;
Switch off the device via the control input.
;
Do not switch the motor (e.g. in cyclic operation) on and off via power
supply.
Switching off the device for maintenance:
;
Switch off the device via the control input.
;
Do not switch the motor (e.g. in cyclic operation) on and off via power
supply.
;
Disconnect the device from the power supply.
;
When disconnecting, be sure to disconnect the ground connection last.
5. INTEGRATED PROTECTIVE FEATURES
The integrated protective functions cause the motor to switch off
automatically in the event of the faults described in the table.
Fault
Safety feature description/
function
Rotor position detection error
An automatic restart follows.
Blocked rotor
;
After the blockage is
removed, the motor restarts
automatically.
Line undervoltage (line voltage
outside of permitted nominal
voltage range)
;
If the line voltage returns to
permitted values, the motor
restarts automatically.
Item no. 50145-5-9970 · ENU · Change 88831 · Approved 2016-04-05 · Page 10 / 12