Operating instructions

S3G710-AO81-01

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G112-IA

Phase

3~

Nominal voltage / VAC

400

Nominal voltage
range / VAC

380 .. 480

Frequency / Hz

50/60

Method of obtaining
data

ml

Speed / min

-1

900

Power consumption / W

930

Current draw / A

1.5

Max. back pressure / Pa

125

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

60

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Data according to ErP Directive

Actual

Req. 2015

01 Overall efficiency η

es

/ %

41.9

33.3

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

48.6

40

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
product's rating label.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart
· HRA 590344
D-74673 Mulfingen

08 Type

S3G710-AO81-01

09 Power consumption P

ed

/ kW

0.86

09 Air flow q

v

/ m³/h

11370

09 Pressure increase total p

sf

/

Pa

105

10 Speed n / min

-1

905

11 Specific ratio

*

1.00

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data obtained at optimum efficiency level. The ErP data is determined using a motor-impeller

combination in a standardized measurement setup.

3.4 Technical description

Weight

19.3 kg

Fan size

710 mm

Rotor surface

Painted black

Electronics housing
material

Die-cast aluminum

Blade material

Sheet aluminum insert, sprayed with PP
plastic

Guard grille material

Steel, coated with black plastic (RAL
9005)

Number of blades

5

Blade pitch

Airflow direction

"V"

Direction of rotation

Counterclockwise, viewed toward rotor

Degree of protection

IP54

Insulation class

"B"

Moisture (F) /
Environmental (H)
protection class

F4-1

Installation position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensation
drainage holes

On rotor side

Mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 10 mA
- Alarm relay
- Integrated PID controller
- Motor current limitation
- PFC, passive
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from supply
- Thermal overload protection for
electronics/motor
- Line undervoltage / phase failure
detection

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Motor protection

Thermal overload protector (TOP)
internally connected

with cable

Variable

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 61800-5-1; CE

Approval

CCC; EAC

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

Item no. 50144-5-9970 · ENU · Change 89187 · Approved 2016-04-15 · Page 5 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

[email protected]  

Содержание S3G710-AO81-01

Страница 1: ...tably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation in the final product Note the following when working on the device...

Страница 2: ...or the impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be ejected and cause injuries Take appropriate safety measures WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can be...

Страница 3: ...ions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Operation in medical equipment with a life sustaining or life support function Operation with external vibrations Conveying solids in the flow medium Painting the device Connections e g screws coming lo...

Страница 4: ...s in mm 1 Direction of air flow V 2 Cable PVC AWG18 6x crimped ferrules 3 Cable PVC AWG22 3x crimped ferrules Item no 50144 5 9970 ENU Change 89187 Approved 2016 04 15 Page 4 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com zakaz ventilatorry ru ...

Страница 5: ...ermined using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 19 3 kg Fan size 710 mm Rotor surface Painted black Electronics housing material Die cast aluminum Blade material Sheet aluminum insert sprayed with PP plastic Guard grille material Steel coated with black plastic RAL 9005 Number of blades 5 Blade pitch 0 Airflow direction V Direction of...

Страница 6: ...guard grille Strictly avoid shocks Wear safety shoes and cut resistant safety gloves CAUTION Heavy load when unpacking device Risk of physical injury such as back injuries Two people should work together to remove the device from its packaging Check the device for transport damage Damaged devices are not to be installed Install the undamaged device in accordance with your application CAUTION Possi...

Страница 7: ... 380 480 VAC 20 A 20 A C20A 2 5 14 3 PE AC 380 480 VAC 25 A 25 A C25A 4 0 12 3 PE AC 380 480 VAC 32 A 30 A C32A 6 0 10 AWG American Wire Gauge 4 2 3 Reactive currents Because of the EMC filter integrated for compliance with EMC limits interference emission and immunity to interference reactive currents can be measured in the supply line even when the motor is at a standstill and the line voltage i...

Страница 8: ... 2 Cable routing for fans installed upright The cables must always be routed downward Item no 50144 5 9970 ENU Change 89187 Approved 2016 04 15 Page 8 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com zakaz ventilatorry ru ...

Страница 9: ...2 A max 250 VAC min 10 mA AC1 1 7 NC white 2 Floating status contact break for failure 2 8 0 10 V yellow Control input set value 0 10 VDC impedance 100 kΩ SELV 2 10 P orange Do not use 2 11 10 V red Voltage output 10 VDC 3 max 10 mA power supply for external devices e g potentiometer SELV 2 12 GND blue Reference ground for control interface SELV Item no 50144 5 9970 ENU Change 89187 Approved 2016 ...

Страница 10: ...ion error An automatic restart follows Blocked rotor After the blockage is removed the motor restarts automatically Line undervoltage line voltage outside of permitted nominal voltage range If the line voltage returns to permitted values the motor restarts automatically Phase failure A phase of the supply voltage fails for at least 5 s When all phases are correctly supplied again the motor automat...

Страница 11: ...t use any pointed or sharp edged objects for cleaning 6 2 Safety inspection NOTE High voltage test The integrated EMC filter has Y capacitors The tripping current is exceeded when AC testing voltage is applied Test the device with DC voltage when you perform the legally required high voltage test The voltage to be used corresponds to the peak value of the AC voltage required by the standard What t...

Страница 12: ...erials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminum Non ferrous metal e g motor windings Plastics particularly with brominated flame retardants in accordance with marking Insulating materials Cables and wires Electronic scrap e g circuit boards Only ferrite magnets and not rare earth magnets are used in ...

Отзывы: