ebm-papst S3G400-ZF03-01 Скачать руководство пользователя страница 6

Operating instructions

S3G400-ZF03-01

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G074-DF

Phase

1~

Nominal voltage / VAC

230

Nominal voltage
range / VAC

200 .. 240

Frequency / Hz

50/60

Method of obtaining
data

ml

Speed (rpm) / min

-1

1200

Power consumption / W

165

Current draw / A

1.3

Max. back pressure / Pa

135

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

60

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Data according to Commission Regulation (EU) 327/
2011

Actual

Req. 2015

01 Overall efficiency η

es

/ %

48.2

28.7

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

59.5

40

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
product's rating label.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart ·
HRA 590344
D-74673 Mulfingen

08 Type

S3G400-ZF03-01

09 Power consumption P

ed

/ kW

0.16

09 Air flow q

v

/ m³/h

2615

09 Pressure increase total p

fs

/

Pa

98

10 Speed (rpm) n / min

-1

1255

11 Specific ratio

*

1.00

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data obtained at optimum efficiency level. The ErP data is determined using a motor-impeller

combination in a standardized measurement setup.

3.4 Technical description

Weight

5.64 kg

Size

400 mm

Motor size

74

Rotor surface

Thick-film passivated

Terminal box material

PP plastic

Impeller material

PP plastic, galvanized sheet-metal plate

Guard grille material

Steel, coated with black plastic (RAL
9005)

Number of blades

5

Airflow direction

V

Direction of rotation

Clockwise, viewed toward rotor

Degree of protection

IP54

Insulation class

"B"

Moisture (F) /
Environmental (H)
protection class

H1

Installation position

Shaft horizontal or rotor on bottom; rotor
on top on request

Cooling hole/opening

On rotor side

Mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 10 mA
- Tach output
- Power limiter
- Motor current limitation
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Overvoltage detection
- Thermal overload protection for
electronics/motor
- Line undervoltage detection

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Electrical hookup

Terminal box

Motor protection

Electronic motor protection

with cable

Variable

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 60034-1; EN 60204-1; EN 60335-1;
CE

Approval

CSA C22.2 No. 77 + CAN/CSA-
E60730-1; UL 1004-7 + 60730-1; EAC

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

;

Use the device in accordance with its degree of protection.

Item no. 57588-5-9970 · ENU · Change 232521 · Approved 2021-05-28 · Page 6 / 13

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание S3G400-ZF03-01

Страница 1: ...nical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation in the final product The locally applicable industrial safety regulations are always to be observed when work...

Страница 2: ...C compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become entangled and be pulled into the de...

Страница 3: ... be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fan from the customer installation Operation in medical equipment with a life sustaining or life support function Conveying solids in the flow medium Painting the device Connections e g screws coming l...

Страница 4: ... Tightening torque 1 5 0 2 Nm 3 Cable diameter max 7 5 mm tightening torque 1 3 0 2 Nm 4 Accessory part Inlet ring 40100 2 4013 not included in scope of delivery Item no 57588 5 9970 ENU Change 232521 Approved 2021 05 28 Page 4 13 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 5: ...ting instructions All dimensions in mm Inlet ring 40100 2 4013 Item no 57588 5 9970 ENU Change 232521 Approved 2021 05 28 Page 5 13 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 6: ... impeller combination in a standardized measurement setup 3 4 Technical description Weight 5 64 kg Size 400 mm Motor size 74 Rotor surface Thick film passivated Terminal box material PP plastic Impeller material PP plastic galvanized sheet metal plate Guard grille material Steel coated with black plastic RAL 9005 Number of blades 5 Airflow direction V Direction of rotation Clockwise viewed toward ...

Страница 7: ...ion Bearing damage shorter service life The fan must not be subjected to force or excessive vibration from sections of the installation If the fan is connected to air ducts the connection should be isolated from vibration e g using compensators or similar elements Ensure stress free attachment of the fan to the substructure Check the device for transport damage Damaged devices are not to be instal...

Страница 8: ... standstill and the line voltage is switched on The values are typically in the range 50 mA At the same time the effective power in this operating state operational readiness is typically 2 W 4 2 3 Residual current circuit breaker RCCB If the use of a residual current device RCD is required in your installation only pulse current sensitive and or AC DC sensitive residual current devices type A or ...

Страница 9: ...is not possible a drip edge can be produced by fitting a cable tie directly in front of the cable gland for example Fans installed lying flat Make sure the cable is routed in a U shaped loop Fig 2 Fan installed lying flat cable routed in a U shaped loop Fans installed upright When routing the cable make sure that the cable glands are located at the bottom The cables must always be routed downward ...

Страница 10: ...12 PE green yellow Ground connection 2 0 10V PWM yellow 0 10 V PWM control input Ri 100 kΩ SELV 4 Tach white Tach output open collector 1 pulse per revolution Isink max 10 mA SELV 3 10 V red Fixed voltage output 10 VDC 3 Imax 10 mA short circuit proof power supply for ext devices e g pot SELV 1 GND blue Reference ground for control interface SELV Item no 57588 5 9970 ENU Change 232521 Approved 202...

Страница 11: ...upply Switching off the device for maintenance Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the power supply When disconnecting be sure to disconnect the ground connection last 5 INTEGRATED PROTECTIVE FEATURES The integrated protective functions cause the motor to switch off automatically in the e...

Страница 12: ...hat period contact ebm papst Adapt the maintenance intervals to the actual level of dust exposure 6 2 Safety inspection NOTE High voltage test The integrated EMC filter has Y capacitors The tripping current is exceeded when AC testing voltage is applied Test the device with DC voltage when you perform the legally required high voltage test The voltage to be used corresponds to the peak value of th...

Страница 13: ...inum Non ferrous metal e g motor windings Plastics particularly with brominated flame retardants in accordance with marking Insulating materials Cables and wires Electronic scrap e g circuit boards Only ferrite magnets and not rare earth magnets are used in external rotor motors from ebm papst Mulfingen GmbH Co KG Ferrite magnets can be disposed of in the same way as normal iron and steel Electric...