4. CONNECTION AND STARTUP

4.1 Mechanical connection

CAUTION
Cutting and crushing hazard when removing fan from
packaging

→ Carefully remove the device from its packaging, by the

guard grille. Strictly avoid shocks.

→ Wear safety shoes and cut-resistant safety gloves.

NOTE
Damage to the device from vibration

Bearing damage, shorter service life
→ The fan must not be subjected to force or excessive vibration

from sections of the installation.

→ If the fan is connected to air ducts, the connection should

be isolated from vibration, e.g. using compensators or similar
elements.

→ Ensure stress-free attachment of the fan to the

substructure.

;

Check the device for transport damage. Damaged devices are not to
be installed.

;

Install the undamaged device in accordance with your application.

CAUTION
Possible damage to the device

If the device slips during installation, serious damage can result.
→ Ensure that the device is securely positioned at its place of

installation until all fastening screws have been tightened.

The fan must not be strained on fastening.

4.2 Electrical connection

DANGER
Voltage on the device

Electric shock
→ Always connect a protective earth first.
→ Check the protective earth.

DANGER
Faulty insulation

Risk of fatal injury from electric shock
→ Use only cables that meet the specified installation

regulations for voltage, current, insulation material, capacity,
etc.

→ Route cables so that they cannot be touched by any

rotating parts.

DANGER
Electrical charge (>50 µC) between phase conductor and
protective earth connection after switching off supply
with multiple devices connected in parallel.

Electric shock, risk of injury
→ Ensure sufficient protection against accidental contact.

Before working on the electrical hookup, short the supply
and PE connections.

CAUTION
Voltage

The fan is a built-in component and has no disconnecting switch.
→ Only connect the fan to circuits that can be switched off with

an all-pole disconnection switch.

→ When working on the fan, secure the system/machine in

which the fan is installed so as to prevent it from being
switched back on.

CAUTION
Electric shock

Voltage on metal part
→ Use the device only with the cable guard and terminal box

intended for it.

NOTE
Water ingress into wires or cables

Water ingress at the customer end of the cable can damage the
device.
→ Make sure the end of the cable is connected in a dry

environment.

Only connect the device to circuits that can be switched off with
an all-pole disconnection switch.

4.2.1 Requirements

;

Check whether the information on the nameplate matches the
connection data.

;

Before connecting the device, make sure the power supply matches
the device voltage.

;

Only use cables designed for the current level indicated on the
nameplate.
For determining the cross-section, note the sizing criteria according
to EN 61800-5-1. The protective earth must have a cross-section
equal to or greater than that of the phase conductor.
We recommend the use of 105 °C cables. Ensure that the minimum
cable cross-section is at least
AWG 26 / 0.13 mm².

Protective earth contact resistance according to EN 60335

Compliance with the resistance specifications according to EN 60335 for
the protective earth connection circuit must be verified in the end
application. Depending on the installation situation, it may be necessary
to connect an additional protective earth conductor by way of the extra
protective earth terminal provided on the device.

4.2.2 Reactive currents

Because of the EMC filter integrated for compliance with EMC
limits (interference emission and immunity to interference),
reactive currents can be measured in the supply line even
when the motor is at a standstill and the line voltage is switched
on.

The values are typically in the range < 50 mA

At the same time, the effective power in this operating state
(operational readiness) is typically < 2 W.

Item no. 51450-5-9970 · ENU · Change 210350 · Approved 2020-04-24 · Page 6 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание S3G300-AL11-51

Страница 1: ...thorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation in the final product The locally applicable industrial safety regulations are always to be obser...

Страница 2: ...C compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become entangled and be pulled into the de...

Страница 3: ... be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fan from the customer installation Operation in medical equipment with a life sustaining or life support function Conveying solids in the flow medium Painting the device Connections e g screws coming l...

Страница 4: ...mensions in mm 1 Direction of air flow A 2 Tightening torque 1 5 0 2 Nm 3 Cable diameter 7 5 mm tightening torque 2 0 3 Nm Item no 51450 5 9970 ENU Change 210350 Approved 2020 04 24 Page 4 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 5: ...nection of protective earth Conformity with standards EN 60034 1 EN 60204 1 EN 60335 1 CE Approval CCC With regard to cyclic speed loads note that the rotating parts of the device are designed for a maximum of one million load cycles If you have special questions consult ebm papst for support Use the device in accordance with its degree of protection Information on surface quality The surfaces of ...

Страница 6: ...that can be switched off with an all pole disconnection switch When working on the fan secure the system machine in which the fan is installed so as to prevent it from being switched back on CAUTION Electric shock Voltage on metal part Use the device only with the cable guard and terminal box intended for it NOTE Water ingress into wires or cables Water ingress at the customer end of the cable can...

Страница 7: ...d connections even with device switched off Electric shock Wait five minutes after disconnecting the voltage at all poles before opening the device Remove the cap from the cable gland Only remove caps where cables are fed in Route the wire s not included in scope of delivery into the terminal box First connect the PE protective earth Connect the wires to the corresponding terminals Use a screwdriv...

Страница 8: ... 230 VAC 50 60 Hz see nameplate for voltage range CON 11 N blue Neutral conductor CON 12 PE green yellow Protective earth CON 70 SL brown Speed selection switch open speed 1 switch closed speed 2 Item no 51450 5 9970 ENU Change 210350 Approved 2020 04 24 Page 8 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpap...

Страница 9: ...d close to the fan Before switching on check the device for visible external damage and make sure the protective devices are functional Check the fan s air flow paths for foreign matter and remove any foreign matter found Apply the nominal supply voltage Start the device by changing the input signal NOTE Damage to the device from vibration Bearing damage shorter service life Low vibration operatio...

Страница 10: ...ency of checking is to be adapted accordingly depending on the degree of soiling DANGER Risk of injury from rotating fan Only clean when not in motion Do not disconnect the fan from the power supply just switch it off via the control input This will prevent start up of the fan Dirt deposits on the motor housing can cause overheating of the motor Soiling of the impeller can cause vibration that wil...

Страница 11: ... heeded 6 3 2 Disassembly Disassembly of the product must be performed or supervised by qualified personnel with the appropriate technical knowledge The product is to be disassembled into suitable components for disposal employing standard procedures for motors WARNING Heavy parts of the product may drop off Some of the product components are heavy These components could drop off during disassembl...

Отзывы: