Operating instructions

S3G300-AL11-50

Translation of the original operating instructions

4.2.3 Residual current circuit breaker (RCCB)

If the use of a residual current device (RCD) is required in your
installation, only pulse-current sensitive and/or AC/DC-
sensitive residual current devices (type A or B) are
permissible. As with variable frequency drives, residual current
devices cannot provide personal safety while operating the
device. When the device power supply is switched on, pulsed
charging currents from the capacitors in the integrated EMC
filter can lead to the instant tripping of residual current devices.
We recommend the use of residual current circuit breakers
(RCCB) with a trip threshold of 300 mA and delayed tripping
(super-resistant, characteristic K).

4.2.4 Locked-rotor protection

Due to the locked-rotor protection, the starting current (LRA) is
equal to or less than the nominal current (FLA).

4.3 Connection in terminal box

4.3.1 Preparing cables for connection

Only strip the cable as far as necessary, ensuring that the cable gland is
sealed and there is no strain on the connections. For tightening torques,
see Chapter 3.1 Product drawing.

NOTE
Tightness and strain relief are dependent on the cable
used.

→ This must be checked by the user.

4.3.2 Connecting wires to terminals

WARNING
Live terminals and connections even with device
switched off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

;

Remove the cap from the cable gland.

Only remove caps where cables are fed in.

;

Route the wire(s) (not included in scope of delivery) into the terminal
box.

;

First connect the "PE" (protective earth).

;

Connect the wires to the corresponding terminals.

Use a screwdriver to do so.
When connecting, ensure that no wire ends fan out.

;

Seal the terminal box.

4.3.3 Cable routing

Water must be prevented from reaching the cable gland along the cable.

NOTE
Damage caused by moisture penetration.

Moisture can penetrate into the terminal box if water is
constantly present at the cable glands.
→ To prevent the constant accumulation of water at the cable

glands, the cable should be routed in a U-shaped loop
wherever possible.

→ If this is not possible, a drip edge can be produced by

fitting a cable tie directly in front of the cable gland for example.

Fans installed lying flat

Make sure the cable is routed in a U-shaped loop.

Fig. 2: Fan installed lying flat, cable routed in a U-shaped loop.

Fans installed upright

When routing the cable, make sure that the cable glands are located at
the bottom. The cables must always be routed downward.

Fig. 3: Cable routing for fans installed upright.

Item no. 51266-5-9970 · ENU · Change 210350 · Approved 2020-04-24 · Page 7 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание S3G300-AL11-50

Страница 1: ...thorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation in the final product The locally applicable industrial safety regulations are always to be obser...

Страница 2: ...C compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become entangled and be pulled into the de...

Страница 3: ... be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fan from the customer installation Operation in medical equipment with a life sustaining or life support function Conveying solids in the flow medium Painting the device Connections e g screws coming l...

Страница 4: ...sions in mm 1 Direction of air flow V 2 Tightening torque 1 5 0 2 Nm 3 Cable diameter max 7 5 mm tightening torque 1 3 0 2 Nm Item no 51266 5 9970 ENU Change 210350 Approved 2020 04 24 Page 4 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 5: ...e Protection class I with customer connection of protective earth Conformity with standards EN 60034 1 EN 60204 1 EN 60335 1 CE Approval CCC With regard to cyclic speed loads note that the rotating parts of the device are designed for a maximum of one million load cycles If you have special questions consult ebm papst for support Use the device in accordance with its degree of protection Informati...

Страница 6: ...that can be switched off with an all pole disconnection switch When working on the fan secure the system machine in which the fan is installed so as to prevent it from being switched back on CAUTION Electric shock Voltage on metal part Use the device only with the cable guard and terminal box intended for it NOTE Water ingress into wires or cables Water ingress at the customer end of the cable can...

Страница 7: ...d connections even with device switched off Electric shock Wait five minutes after disconnecting the voltage at all poles before opening the device Remove the cap from the cable gland Only remove caps where cables are fed in Route the wire s not included in scope of delivery into the terminal box First connect the PE protective earth Connect the wires to the corresponding terminals Use a screwdriv...

Страница 8: ... 230 VAC 50 60 Hz see nameplate for voltage range CON 11 N blue Neutral conductor CON 12 PE green yellow Protective earth CON 70 SL brown Speed selection switch open speed 1 switch closed speed 2 Item no 51266 5 9970 ENU Change 210350 Approved 2020 04 24 Page 8 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpap...

Страница 9: ...d close to the fan Before switching on check the device for visible external damage and make sure the protective devices are functional Check the fan s air flow paths for foreign matter and remove any foreign matter found Apply the nominal supply voltage Start the device by changing the input signal NOTE Damage to the device from vibration Bearing damage shorter service life Low vibration operatio...

Страница 10: ...ency of checking is to be adapted accordingly depending on the degree of soiling DANGER Risk of injury from rotating fan Only clean when not in motion Do not disconnect the fan from the power supply just switch it off via the control input This will prevent start up of the fan Dirt deposits on the motor housing can cause overheating of the motor Soiling of the impeller can cause vibration that wil...

Страница 11: ... heeded 6 3 2 Disassembly Disassembly of the product must be performed or supervised by qualified personnel with the appropriate technical knowledge The product is to be disassembled into suitable components for disposal employing standard procedures for motors WARNING Heavy parts of the product may drop off Some of the product components are heavy These components could drop off during disassembl...

Отзывы: