ebm-papst S1G300-DN01-02 Скачать руководство пользователя страница 5

Operating instructions

S1G300-DN01-02

Translation of the original operating instructions

3.2 Nominal data

Motor

M1G055-DF

Phase

1~

1~

Nominal voltage / VAC

230

230

Nominal voltage
range / VAC

200 .. 240

200 .. 240

Frequency / Hz

50/60

50/60

Method of obtaining
data

ml

Speed (rpm) / min

-1

1400

1100

Power consumption / W

62

Current draw / A

0.55

Max. back pressure / Pa

55

Min. ambient
temperature / °C

-40

-40

Max. ambient
temperature / °C

40

40

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Technical description

Weight

1.6 kg

Size

300 mm

Motor size

55

Rotor surface

Thick-film passivated

Blade material

PP plastic

Number of blades

5

Airflow direction

A

Direction of rotation

Clockwise, viewed toward rotor

Degree of protection

IP54

Insulation class

"B"

Moisture (F) /
Environmental (H)
protection class

H1+

Installation position

Shaft horizontal

Condensation
drainage holes

None, open rotor

Mode

S1

Motor bearing

Ball bearing with low-temperature lubricant

Technical features

- Speed setting input (230 V)
- Power limiter
- Motor current limitation
- Soft start
- Thermal overload protection for motor

Speed levels

2

Motor protection

Thermal overload protector (TOP)
internally connected

with cable

Lateral

Protection class

II

Conformity with
standards

CE

Approval

CCC; EAC

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

;

Use the device in accordance with its degree of protection.

Information on surface quality

The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may change during the production period.
This has no effect on strength, dimensional stability and dimensional
accuracy.
The color pigments in the paints used perceptibly react to UV light over
the course of time. This does not however in any way affect the
technical properties of the products. The product is to be protected against
UV radiation to prevent the formation of patches and fading. Changes in
color are not a reason for complaint and are not covered by the warranty.

3.4 Mounting data

;

Secure the screws against unintentional loosening (e.g. use self-
locking screws).

For screw clearance, see Chapter 3.1 Product drawing

Strength class of
screws

8.8

Any further mounting data required can be taken from the product
drawing or Section Chapter 4.1 Mechanical connection.

3.5 Transport and storage conditions

Max. permitted
ambient temp. for
motor (transport/
storage)

+ 80 °C

Min. permitted
ambient temp. for
motor (transport/
storage)

- 40 °C

3.6 Electromagnetic compatibility

EMC immunity to
interference

According to EN 61000-6-2 (industrial
environment)

EMC circuit feedback

According to EN 61000-3-2/3

EMC interference
emission

According to EN 61000-6-3 (household
environment)

Item no. 54235-5-9970 · ENU · Change 202174 · Approved 2019-01-04 · Page 5 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание S1G300-DN01-02

Страница 1: ...nd authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation in the final product The locally applicable industrial safety regulations are always to be ...

Страница 2: ...Electrical or electromagnetic interference after installing the device in customer equipment Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNI...

Страница 3: ...uld be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fan from the customer installation Operation in medical equipment with a life sustaining or life support function Conveying solids in the flow medium Painting the device Connections e g screws comin...

Страница 4: ... Product drawing All dimensions in mm 1 Direction of air flow A 2 Cable PVC AWG18 3x crimped splices Item no 54235 5 9970 ENU Change 202174 Approved 2019 01 04 Page 4 10 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 5: ... have special questions consult ebm papst for support Use the device in accordance with its degree of protection Information on surface quality The surfaces of the products conform to the generally applicable industrial standard The surface quality may change during the production period This has no effect on strength dimensional stability and dimensional accuracy The color pigments in the paints ...

Страница 6: ...om being switched back on NOTE Water ingress into wires or cables Water ingress at the customer end of the cable can damage the device Make sure the end of the cable is connected in a dry environment Only connect the device to circuits that can be switched off with an all pole disconnection switch NOTE Cable routing Always route cables downward so that no condensation can run along the cable towar...

Страница 7: ...ating instructions 4 4 Connection diagram Drawing preliminary Item no 54235 5 9970 ENU Change 202174 Approved 2019 01 04 Page 7 10 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 8: ...in the event of the faults described in the table Fault Safety feature description function Rotor position detection error An automatic restart follows Blocked rotor After the blockage is removed the motor restarts automatically Motor overload After cooling off the device restarts automatically 6 MAINTENANCE MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perform any repairs on your device Send t...

Страница 9: ...ace device 6 3 Disposal For ebm papst environmental protection and resource preservation are top priority corporate goals ebm papst operates an environmental management system which is certified in accordance with ISO 14001 and rigorously implemented around the world on the basis of German standards Right from the development stage ecological design technical safety and health protection are fixed...

Страница 10: ...ws Miscellaneous insulators used in the terminal box Power cables Cables for internal wiring Electrolytic capacitors Dispose of electronic components employing the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 54235 5 9970 ENU Change 202174 Approved 2019 01 04 Page 10 10 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone...

Отзывы: