Operating instructions

R3G560-RB32-01

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G150-IF

Phase

3~

Nominal voltage / VAC

400

Nominal voltage
range / VAC

380 .. 480

Frequency / Hz

50/60

Type of data definition

ml

Speed / min

-1

1650

Power input / W

2900

Current draw / A

4.43

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

50

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Data according to ErP directive

Measurement category

A

Efficiency category

Static

Variable speed drive

Yes

Specific ratio

*

1.01

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Actual

Request
2013

Request
2015

Overall efficiency η

es

/ %

66.9

52.4

56.4

Efficiency grade N

72.5

58

62

Power input P

ed

/ kW

2.93

Air flow q

v

/ m³/h

9440

Pressure increase total p

sf

/ Pa

710

Speed n / min

-1

1655

Data definition with optimum efficiency.

The ErP data is determined using a motor-impeller combination in a standardised

measurement configuration.

3.4 Technical features

Mass

27.8 kg

Size

560 mm

Surface of rotor

Coated in black

Material of electronics
housing

Die-cast aluminium

Material of impeller

PP plastic

Number of blades

6

Direction of rotation

Clockwise, seen on rotor

Type of protection

IP 54

Insulation class

"F"

Humidity class

F4-1

Mounting position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensate discharge
holes

Rotor-side

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA
- Output for slave 0-10 V
- Operation and alarm display
- Input for sensor 0-10 V or 4-20 mA
- External 24 V input (programming)
- External release input
- Alarm relay
- Integrated PID controller
- Motor current limit
- PFC, passive
- RS485 MODBUS RTU
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Over-temperature protected
electronics / motor
- Line undervoltage / phase failure
detection

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical leads

Via terminal box

Motor protection

Reverse polarity and locked-rotor
protection

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 61800-5-1; CE

Approval

C22.2 Nr.77 + CAN/CSA-E60730-1;
UL 1004-7 + 60730

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.5 Mounting data

;

Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

3.6 Transport and storage conditions

;

Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+80 °C

Min. permissible
ambient motor temp.
(transp./storage)

-40 °C

Item no. 52110-5-9970 · ENG · Revision 85863 · Release 2015-06-26 · Page 5 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание R3G560-RB32-01

Страница 1: ...e to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device Observe the following when working on the unit Do not make any modifications additions or conversions to the device without the approval of ebm papst 1 4 Electrical voltag...

Страница 2: ... on the system machine wait until all parts have come to a standstill DANGER Flying parts Missing safety devices may cause balancing weights or broken fan blades to be ejected at high speeds causing bodily harm Take appropriate safety measures WARNING Rotating device Long hair loose items of clothing and jewellery could become entangled and pulled into the device You could be injured Do not wear a...

Страница 3: ...ice in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustaining or lifesaving function Operation with external vibrations Moving solids content in flow medium Painting the device Connections e g screws coming loose during operation Opening the terminal box du...

Страница 4: ...482 2 4013 not included in the standard scope of delivery 2 Depth of screw max 25 mm 3 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 4 Tightening torque 3 5 0 5 Nm Item no 52110 5 9970 ENG Revision 85863 Release 2015 06 26 Page 4 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 5: ...l features Output 10 VDC max 10 mA Output 20 VDC max 50 mA Output for slave 0 10 V Operation and alarm display Input for sensor 0 10 V or 4 20 mA External 24 V input programming External release input Alarm relay Integrated PID controller Motor current limit PFC passive RS485 MODBUS RTU Soft start Control input 0 10 VDC PWM Control interface with SELV potential safely disconnected from the mains O...

Страница 6: ... must no longer be installed Install the undamaged device according to your application 4 2 Connecting the electrical system DANGER Electric voltage on the device Electric shock Always install a protective earth first Check the protective earth DANGER Incorrect insulation Risk of fatal injury from electric shock Use only cables that meet the specified installation requirements for voltage current ...

Страница 7: ...VAC 16 A 15 A C16A 1 5 16 3 PE AC 380 480 VAC 20 A 20 A C20A 2 5 14 3 PE AC 380 480 VAC 25 A 25 A C25A 4 0 12 3 PE AC 380 480 VAC 32 A 30 A C32A 6 0 10 AWG American Wire Gauge 4 2 3 Idle current Because of the EMC filter integrated for compliance with EMC limits interference emission and interference immunity idle currents in the mains cable can be measured even when the motor is at a standstill a...

Страница 8: ...hat no cables splice off Fig 2 Connecting the wires to terminals Seal the terminal box 4 3 3 Cable routing No water may penetrate along the cable in the direction of the cable gland When routing the cable ensure that the screwed cable glands are arranged at the bottom The cables must always be routed downwards Fig 3 Cable routing for fans installed upright 4 4 Factory settings Factory settings wit...

Страница 9: ...en pin or applied voltage 5 50 VDC disabling bridge to GND or applied voltage 1 VDC reset function triggers software reset after a level change to 1 VDC SELV KL 3 8 Din2 Digital input 2 parameter set switch 1 2 according to EEPROM setting the valid used parameter set can be selected via bus or via digital input DIN2 Parameter set 1 open pin or applied voltage 5 50 VDC Parameter set 2 bridge to GND...

Страница 10: ...the fan for foreign objects and remove any that are found Apply the nominal voltage to the voltage supply Start the device by changing the input signal 4 8 Switching off the device Switching off the device during operation Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Switching off the device for maintenance work Switch off ...

Страница 11: ...ply Important The error message resets automatically The device starts up again automatically without advance warning Faulty connection De energise correct connection see connection diagram Motor winding broken Replace device Insufficient cooling Improve cooling Let the device cool down To reset the error message switch off the mains supply voltage for a min of 25 s and switch it on again Alternat...

Страница 12: ...nt of the device Check the device for damage to blades and housing Visual inspection At least every 6 months Replacement of the device Mounting the connection lines Visual inspection At least every 6 months Fasten Check the insulation of the wires for damage Visual inspection At least every 6 months Replace wires Impeller for wear deposits corrosion and damage Visual inspection At least every 6 mo...