background image

Operating instructions

R3G560-PB31-03

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G150-IF

Phase

3~

Nominal voltage / VAC

400

Nominal voltage
range / VAC

380 .. 480

Frequency / Hz

50/60

Method of obtaining
data

ml

Speed (rpm) / min

-1

1700

Power consumption / W

4250

Current draw / A

6.5

Min. ambient
temperature / °C

-40

Max. ambient
temperature / °C

40

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

Occasional start-up at temperatures between -40 °C and -25 °C is
permitted. For continuous operation at ambient temperatures below -25
°C (such as refrigeration applications), a fan design with special low-
temperature bearings must be used.

3.3 Data according to Commission Regulation (EU) 327/
2011

Actual

Req. 2015

01 Overall efficiency η

es

/ %

70.1

58

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

74.1

62

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
product's rating label.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart ·
HRA 590344
D-74673 Mulfingen

08 Type

R3G560-PB31-03

09 Power consumption P

ed

/ kW

4.15

09 Air flow q

v

/ m³/h

9600

09 Pressure increase total p

fs

/

Pa

1052

10 Speed (rpm) n / min

-1

1695

11 Specific ratio

*

1.01

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data obtained at optimum efficiency level. The efficiency values displayed for achieving

conformity with the Ecodesign Regulation EU 327/2011 has been reached with defined air

duct components (e.g. inlet rings). The dimensions must be requested from ebm-papst. If

other air conduction geometries are used on the installation side, the ebm-papst evaluation

loses its validity/the conformity must be confirmed again. The product does not fall within

the scope of Regulation (EU) 2019/1781 due to the exception specified in Article 2 (2a)

(motors completely integrated into a product).

3.4 Technical description

Weight

27 kg

Size

560 mm

Motor size

150

Rotor surface

Painted black

Electronics housing
material

Die-cast aluminum

Impeller material

Sheet aluminum

Number of blades

5

Direction of rotation

Clockwise, viewed toward rotor

Degree of protection

IP55

Insulation class

"F"

Moisture (F) /
Environmental (H)
protection class

H1

Ambient temperature
note

Occasional start-up at temperatures
between -40°C and -25°C is permitted.
For continuous operation at ambient
temperatures below -25°C (such as
refrigeration applications), use must be
made of a fan design with special low-
temperature bearings.

Installation position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensation
drainage holes

On rotor side

Mode

S1

Motor bearing

Ball bearing

Technical features

- Operation and alarm display with LED
- External 15-50 VDC input
(parameterization)
- Alarm relay
- Integrated PI controller
- Configurable inputs/outputs (I/O)
- MODBUS V6.3
- Motor current limitation
- RS-485 MODBUS-RTU
- Soft start
- Voltage output 3.3-24 VDC, Pmax =
800 mW
- Control interface with SELV potential
safely disconnected from the mains
- Thermal overload protection for
electronics/motor
- Line undervoltage / phase failure
detection

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Electrical hookup

Terminal box

Motor protection

Reverse polarity and locked-rotor
protection

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 61800-5-1; CE

Approval

CSA C22.2 No. 77 + CAN/CSA-
E60730-1; UL 1004-7 + 60730-1; EAC

Item no. 55780-5-9970 · ENU · Change 209539 · Approved 2021-02-01 · Page 6 / 17

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание R3G560-PB31-03

Страница 1: ...a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation in the final product The locally applicable industrial safety regulations are always to be observed when working on the device Keep the workplace clean and tidy Untidiness in the work area increases...

Страница 2: ...e come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be ejected and cause injuries Take appropriate safety measures WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become entangled and be pulled into the device Injuries can result Do not wear any loose fitting or dangling clothing or jew...

Страница 3: ...ng the operating instructions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fan from the customer installation Operation in medical equipment with a life ...

Страница 4: ...learance for screw 20 mm 3 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm The tightening torque is designed for PVC cables If the cable materials are different the tightening torque may have to be adjusted 4 Tightening torque 1 5 0 2 Nm Item no 55780 5 9970 ENU Change 209539 Approved 2021 02 01 Page 4 17 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 ...

Страница 5: ...s All dimensions in mm Inlet ring 64030 2 4013 with pressure tap k factor 348 Item no 55780 5 9970 ENU Change 209539 Approved 2021 02 01 Page 5 17 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 6: ...s The dimensions must be requested from ebm papst If other air conduction geometries are used on the installation side the ebm papst evaluation loses its validity the conformity must be confirmed again The product does not fall within the scope of Regulation EU 2019 1781 due to the exception specified in Article 2 2a motors completely integrated into a product 3 4 Technical description Weight 27 k...

Страница 7: ...greater than or equal to 250 times the rated output of the arrangement It is the responsibility of the installation engineer or operator owner of the device to ensure if necessary after consultation with the network operator that this device is only connected to a connection point with an Ssc value greater than or equal to 250 times the rated output of the arrangement 4 CONNECTION AND STARTUP 4 1 ...

Страница 8: ...e necessary to connect an additional protective earth conductor by way of the extra protective earth terminal provided on the device The protective earth terminal is located on the housing and provided with a protective earth symbol and a hole 4 2 2 Supply connection and fuses Assignment of supply cable cross sections and their required fuses line protection only no equipment protection Nominal vo...

Страница 9: ... of the drive and the type of cable routing see Chapter 4 2 2 Supply connection and fuses Control and relay cables min max Rigid cable cross section 0 2 mm 1 5 mm Flexible cable cross section 0 2 mm 1 5 mm AWG kcmil cable cross section 24 16 Wire end ferrules with insulating collar in accordance with DIN 46228 4 for flexible cable 0 14 mm 0 75 mm Wire end ferrules without insulating collar in acco...

Страница 10: ...ght Fit the terminal box cover making sure that the sealing surfaces are clean Screw in the four screws for tightening torque see Chapter 3 1 Product drawing 4 3 4 Cable routing Water must be prevented from reaching the cable gland along the cable NOTE Damage caused by moisture penetration Moisture can penetrate into the terminal box if water is constantly present at the cable glands To prevent th...

Страница 11: ...teristic curve P1 IN SELV CON2 IO3 Function parameterizable see Optional interface functions table Factory setting Analog output 0 10 V max 5 mA function Fan modulation level Characteristic curve parameterizable see output characteristic curve P3 OUT SELV CON2 Vout Voltage output 3 3 24 VDC 5 Pmax 800 mW voltage parameterizable Factory setting 10 VDC short circuit proof supply for external devices...

Страница 12: ...D159 0 Ain2 0 10V PWM analog input D159 2 Ri 100K characteristic curve parameterizable f PWM 1k 10KHz SELV Ain2 4 20mA analog input Ri 125R characteristic curve parameterizable SELV D159 3 Din3 active high digital input not active pin open or applied voltage 1 5VDC active applied voltage 3 5 50VDC SELV D15A 0 Din3 active low digital input not active pin open or applied voltage 3 5 50VDC active app...

Страница 13: ... operating instructions 4 7 Equivalent circuit diagrams Item no 55780 5 9970 ENU Change 209539 Approved 2021 02 01 Page 13 17 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 14: ...ing Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with excessively high vibration levels can lead to premature failure The maximum permissible vibration severity must not exceed 3 5 mm s and should be checked at intervals of 6 months It is to be determined at the motor mount at the motor support plate at least in axial direction an...

Страница 15: ...ts automatically without warning Faulty connection Isolate from supply correct connection see connection diagram Broken motor winding Replace device Inadequate cooling Improve cooling Allow the device to cool down Ambient temperature too high Reduce the ambient temperature Allow the device to cool down Impermissible operating point e g back pressure too high Correct the operating point Allow the d...

Страница 16: ...ensors depends on the device concerned and the installation situation 6 3 Cleaning To ensure a long service life check the fans regularly for proper operation and soiling The frequency of checking is to be adapted accordingly depending on the degree of soiling DANGER Risk of injury from rotating fan Only clean when not in motion Do not disconnect the fan from the power supply just switch it off vi...

Страница 17: ...ons for ecological disposal of the product and its components 6 5 1 Country specific legal requirements NOTE Country specific legal requirements Always observe the applicable country specific legal regulations with regard to the disposal of products or waste occurring in the various phases of the life cycle The corresponding disposal standards are also to be heeded 6 5 2 Disassembly Disassembly of...

Отзывы: