background image

Operating instructions

R3G500-RI86-01

Translation of the original operating instructions

4.6 Checking the connections

;

Make sure that the power is off (all phases).

;

Secure it from being switched on again.

;

Check the correct fit of the connection lines.

;

Screw the terminal box cover closed again. Terminal box tightening
torque, see chapter 3.1 Product drawing.

;

Route the connecting cables in the terminal box so that the terminal
box cover closes without resistance.

;

Use all plug screws (the entire number). In doing so, insert the
screws manually to avoid damage to the thread.

;

Make sure that the terminal box is correctly closed and sealed and
that all screws and screwed cable glands are properly tightened.

4.7 Switch on device

The device may only be switched on if it has been installed properly and
in accordance with its intended use, including the required safety
mechanisms and professional electrical connection. This also applies for
devices which have already been equipped with plugs and terminals or
similar connectors by the customer.

WARNING
Hot motor housing

Fire hazard
→ Ensure that no combustible or flammable materials are

located close to the fan.

;

Inspect the device for visible external damage and the proper function
of the protective features before switching it on.

;

Check the air flow paths of the fan for foreign objects and remove any
that are found.

;

Apply the nominal voltage to the voltage supply.

;

Start the device by changing the input signal.

4.8 Switching off the device

Switching off the device during operation:

;

Switch off the device via the control input.

;

Do not switch the motor (e.g. in cyclic operation) on and off via power
supply.

Switching off the device for maintenance work:

;

Switch off the device via the control input.

;

Do not switch the motor (e.g. in cyclic operation) on and off via power
supply.

;

Disconnect the device from the supply voltage.

;

When disconnecting, be sure to disconnect the earth wire connection
last.

5. INTEGRATED PROTECTIVE FUNCTIONS

The integrated protective functions cause the motor to switch off
automatically in case of faults described in the table.

Malfunctions

Description / Function of
safety feature

Rotor position detection error

An automatic restart occurs.

Locked rotor

;

After the blockage is

removed, the motor restarts
automatically.

Line under-voltage (mains input
voltage outside of permitted
nominal voltage)

;

If the mains supply voltage

returns to permitted values, the
motor restarts automatically.

Phase failure

A phase of the supply voltage
fails for at least 5 s.

;

If all phases are correctly

supplied again, the motor
automatically restarts after 10 -
40 s.

Item no. 51606-5-9970 · ENG · Revision 82547 · Release 2014-05-08 · Page 10 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание R3G500-RI86-01

Страница 1: ...itted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device Observe the following when working on the unit Do not make any modifications additions or conversions to the device without the approval of ebm p...

Страница 2: ...rotor and impeller can be injured Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill DANGER Flying parts Missing safety devices may cause balancing weights or broken fan blades to be ejected at high speeds causing bodily harm Take appropriate safety measures WARNING Rotating device Long hair loose items of clothing and j...

Страница 3: ...ice in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustaining or lifesaving function Operation with external vibrations Moving solids content in flow medium Painting the device Connections e g screws coming loose during operation Opening the terminal box du...

Страница 4: ...901 2 2943 not included in the standard scope of delivery 2 Depth of screw max 20 mm 3 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 4 Tightening torque 3 5 0 5 Nm Item no 51606 5 9970 ENG Revision 82547 Release 2014 05 08 Page 4 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 5: ...ing Ball bearing Technical features Output 10 VDC max 10 mA Output 20 VDC max 50 mA Output for slave 0 10 V Input for sensor 0 10 V or 4 20 mA External 24 V input programming External release input Alarm relay Integrated PID controller Motor current limit PFC passive RS485 MODBUS RTU Soft start Control input 0 10 VDC PWM Control interface with SELV potential safely disconnected from the mains Over...

Страница 6: ...must no longer be installed Install the undamaged device according to your application 4 2 Connecting the electrical system DANGER Electric voltage on the device Electric shock Always install a protective earth first Check the protective earth DANGER Incorrect insulation Risk of fatal injury from electric shock Use only cables that meet the specified installation requirements for voltage current i...

Страница 7: ...VAC 16 A 15 A C16A 1 5 16 3 PE AC 380 480 VAC 20 A 20 A C20A 2 5 14 3 PE AC 380 480 VAC 25 A 25 A C25A 4 0 12 3 PE AC 380 480 VAC 32 A 30 A C32A 6 0 10 AWG American Wire Gauge 4 2 3 Idle current Because of the EMC filter integrated for compliance with EMC limits interference emission and interference immunity idle currents in the mains cable can be measured even when the motor is at a standstill a...

Страница 8: ...hat no cables splice off Fig 2 Connecting the wires to terminals Seal the terminal box 4 3 3 Cable routing No water may penetrate along the cable in the direction of the cable gland When routing the cable ensure that the screwed cable glands are arranged at the bottom The cables must always be routed downwards Fig 3 Cable routing for fans installed upright 4 4 Factory settings Factory settings wit...

Страница 9: ...en pin or applied voltage 5 50 VDC disabling bridge to GND or applied voltage 1 VDC reset function triggers software reset after a level change to 1 VDC SELV KL 3 8 Din2 Digital input 2 parameter set switch 1 2 according to EEPROM setting the valid used parameter set can be selected via bus or via digital input DIN2 Parameter set 1 open pin or applied voltage 5 50 VDC Parameter set 2 bridge to GND...

Страница 10: ...e fan for foreign objects and remove any that are found Apply the nominal voltage to the voltage supply Start the device by changing the input signal 4 8 Switching off the device Switching off the device during operation Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Switching off the device for maintenance work Switch off th...

Страница 11: ...cal blockage Mains supply voltage faulty Check mains supply voltage restore power supply Important The error message resets automatically The device starts up again automatically without advance warning Faulty connection De energise correct connection see connection diagram Motor winding broken Replace device Thermal overload protector responded Allow motor to cool off locate and rectify cause of ...

Страница 12: ...he protective casing against accidental contact for damage and to ensure that it is intact Visual inspection At least every 6 months Repair or replacement of the device Check the device for damage to blades and housing Visual inspection At least every 6 months Replacement of the device Mounting the connection lines Visual inspection At least every 6 months Fasten Check the insulation of the wires ...