ebm-papst R3G450-AT09-03 Скачать руководство пользователя страница 5

Operating instructions

R3G450-AT09-03

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G150-FF

Phase

3~

Nominal voltage / VAC

400

Nominal voltage
range / VAC

380 .. 480

Frequency / Hz

50/60

Type of data definition

ml

Speed / min

-1

2150

Power input / W

2700

Current draw / A

4.2

Min. ambient temperature
/ °C

-25

Max. ambient
temperature
/ °C

60

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Data according to ErP directive

Installation category

A

Efficiency category

Static

Variable speed drive

Yes

Specific ratio

*

1.01

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Actual

Request
2013

Request
2015

Overall efficiency η

es

/ %

60.9

52

56

Efficiency grade N

66.9

58

62

Power input P

ed

/ kW

2.7

Air flow q

v

/ m³/h

5770

Pressure increase total p

sf

/ Pa

972

Speed n / min

-1

2165

Data definition with optimum efficiency.

The ErP data is determined using a motor-impeller combination in a standardised

measurement configuration.

3.4 Technical features

Mass

20.6 kg

Size

450 mm

Surface of rotor

Coated in black

Material of electronics
housing

Die-cast aluminium

Material of impeller

Aluminium sheet

Number of blades

6

Direction of rotation

Clockwise, seen on rotor

Type of protection

IP 54

Insulation class

"F"

Humidity class

F4-1

Mounting position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensate discharge
holes

Rotor-side

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA
- Output for slave 0-10 V
- Input for sensor 0-10 V or 4-20 mA
- Alarm relay
- Integrated PID controller
- Motor current limit
- PFC, passive
- RS485 ebmBUS
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Over-temperature protected
electronics / motor
- Line undervoltage / phase failure
detection

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical leads

Via terminal box

Motor protection

Reverse polarity and locked-rotor
protection

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 61800-5-1; CE

Approval

CSA C22.2 Nr.77; EAC; UL 2111; VDE

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.5 Mounting data

;

Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

3.6 Transport and storage conditions

;

Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+80 °C

Min. permissible
ambient motor temp.
(transp./storage)

-40 °C

Item no. 50568-5-9970 · Revision 82549 · Release 2014-05-08 · Page 5 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание R3G450-AT09-03

Страница 1: ...ce to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it i...

Страница 2: ...g on the system machine wait until all parts have come to a standstill DANGER Flying parts Missing safety devices may cause balancing weights or broken fan blades to be ejected at high speeds causing...

Страница 3: ...imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustaining or lifesaving function Operation with external vibrations Moving solids content in flow medium Pai...

Страница 4: ...torque 4 0 6 Nm 2 Accessory part inlet nozzle 63045 2 4013 not included in the standard scope of delivery other inlet nozzles on request 3 Depth of screw max 25 mm 4 Tightening torque 3 5 0 5 Nm Item...

Страница 5: ...ration mode S1 Motor bearing Ball bearing Technical features Output 10 VDC max 10 mA Output 20 VDC max 50 mA Output for slave 0 10 V Input for sensor 0 10 V or 4 20 mA Alarm relay Integrated PID contr...

Страница 6: ...the specified installation requirements for voltage current insulation material load etc Route cables such that they cannot be touched by any rotating parts DANGER Electrical load 50 C between mains...

Страница 7: ...e 4 2 2 Idle current Because of the EMC filter integrated for compliance with EMC limits interference emission and interference immunity idle currents in the mains cable can be measured even when the...

Страница 8: ...must always be routed downwards Fig 3 Cable routing for fans installed upright 4 4 Factory settings Factory settings with which the device is pre set by ebm papst Operation mode PWM controlling Group...

Страница 9: ...quate to 100 level control coefficient KL3 2 8 GND Reference mass for control interface SELV KL3 3 7 0 10 V Use control actual value input 0 10 VDC impedance 100 k only as alternative to 4 20 mA input...

Страница 10: ...re switching it on Check the air flow paths of the fan for foreign objects and remove any that are found Apply the nominal voltage to the voltage supply Start the device by changing the input signal 4...

Страница 11: ...gise correct connection see connection diagram Overtemperature of electronics motor Insufficient cooling Improve cooling Let the device cool down To reset the error message switch off the mains supply...

Страница 12: ...every 6 months Clean or replace impeller Tightness of screwed cable gland Visual inspection At least every 6 months Retighten replace if damaged Condensate discharge holes for clogging as necessary V...

Отзывы: