ebm-papst R3G400-AQ23-01 Скачать руководство пользователя страница 12

Operating instructions

R3G400-AQ23-01

Translation of the original operating instructions

No.

Conn.

Designation

Function/assignment

KL 3

6

Ain1 I

Analog input 1, set value: 4-20 mA, Ri = 100 Ω, adjustable curve, only usable as alternative to input Ain1U;
SELV

KL 3

7

Din1

Digital input 1: enable electronics,
enable: pin open or applied voltage 5-50 VDC
disable: bridge to GND or applied voltage < 1 VDC
reset function: triggers software reset after a level change to < 1 VDC; SELV

KL 3

8

Din2

Digital input 2: Switching parameter sets 1/2, according to EEPROM setting, the valid or used parameter set
can be selected via bus or via digital input DIN2.
Parameter set 1: pin open or applied voltage 5-50 VDC
Parameter set 2: bridge to GND or applied voltage < 1 VDC; SELV

KL 3

9

Din3

Digital input 3: according to EEPROM setting, the integrated controller's direction of action can be selected via
bus or digital input Din3;
normal: pin open or applied voltage 5-50 VDC
inverse: bridge to GND or applied voltage < 1 VDC; SELV

KL 3

11

Ain2 U

Analog input 2, measured value: 0-10 V, Ri = 100 kΩ, adjustable curve, only usable as alternative to input
Ain2I; SELV

KL 3

12

+ 20 V

Fixed voltage output 20 VDC, +20 V +25/-10%, max. 50 mA, short-circuit-proof power supply for external
devices (e.g. sensors); SELV
or: +24 VDC input for parameter setting without line voltage

KL 3

13

Ain2 I

Analog input 2, measured value: 4-20 mA, Ri = 100 Ω, adjustable curve, only usable as alternative to input
Ain2U; SELV

KL 3

14

Aout

Analog output 0-10 VDC, max. 5 mA, output of current motor modulation level / motor speed
adjustable curve; SELV

Item no. 50448-5-9970 · ENU · Change 209539 · Approved 2021-01-29 · Page 12 / 16

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание R3G400-AQ23-01

Страница 1: ...permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the devic...

Страница 2: ...come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be ejected and cause injuries Take appropriate safety measures WARNING Rotatin...

Страница 3: ...e In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation...

Страница 4: ...essure tap k factor 188 not included in scope of delivery 2 Max clearance for screw 25 mm 3 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 4 Tightening torque 3 5 0 5 Nm Item no 50448 5...

Страница 5: ...mm 1 Inlet ring with pressure tap 40075 2 4013 k factor 188 not included in scope of delivery Item no 50448 5 9970 ENU Change 209539 Approved 2021 01 29 Page 5 16 ebm papst Mulfingen GmbH Co KG Bachm...

Страница 6: ...fficiency level The ErP data is determined using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 21 7 kg Size 400 mm Motor size 150 Rotor surface Pain...

Страница 7: ...ensure if necessary after consultation with the network operator that this device is only connected to a connection point with a Ssc value that is greater than or equal to 120 times the rated output...

Страница 8: ...earth terminal provided on the device The protective earth terminal is located on the housing and provided with a protective earth symbol and a hole 4 2 2 Supply connection and fuses Assignment of sup...

Страница 9: ...t included in scope of delivery into the terminal box First connect the PE protective earth Connect the wires to the corresponding terminals Use a screwdriver to do so When connecting ensure that no w...

Страница 10: ...eter set 2 PWM control Fan device address 01 Max PWM 100 Min PWM 5 Save set value to EEPROM Yes Set value requirement Analog linear Direction of action parameter set 1 Positive heating Direction of ac...

Страница 11: ...contact changeover contact common connection contact rating 250 VAC max 2 A AC1 min 10 mA KL2 3 NC Status relay floating status contact break for failure KL 3 1 RSA Bus connection RS485 RSA MODBUS RTU...

Страница 12: ...EEPROM setting the integrated controller s direction of action can be selected via bus or digital input Din3 normal pin open or applied voltage 5 50 VDC inverse bridge to GND or applied voltage 1 VDC...

Страница 13: ...ng Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with excessively high vibration levels can lead to premature failure The maximum per...

Страница 14: ...e from supply and remove mechanical blockage Line voltage faulty Check line voltage restore power supply Attention The error message resets automatically Device restarts automatically without warning...

Страница 15: ...aintenance intervals to the actual level of dust exposure 6 3 Safety inspection NOTE High voltage test The integrated EMC filter has Y capacitors The tripping current is exceeded when AC testing volta...

Страница 16: ...tallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminum Non ferrous metal e g motor windings Plasti...

Отзывы: