ebm-papst R3G400-AM56-11 Скачать руководство пользователя страница 9

Operating instructions

R3G400-AM56-11

Translation of the original operating instructions

4.4 Connection screen

No.

Conn.

Designation

Function / assignment

PE

PE

Protective earth connection

KL1

1, 2

N, L

Supply voltage, 50/60 Hz

KL2

1

NC

Floating status message contact, normally closed connection

KL2

2

COM

Floating status message contact, changeover contact, common connection (2 A, max. 250 VAC,
min. 10 mA, AC1)

KL2

3

NO

Floating status message contact, normally open connection

KL3

1

OUT

Analogue output, 0-10 VDC, max. 3 mA, SELV,
Output of the current motor level control coefficient:
1 V corresponds to 10% level control coefficient,
10 V correspond to 100% level control coefficient.

KL3

2, 8

GND

Reference mass for control interface, SELV

KL3

3, 7

0-10 V

Use control / actual value input 0-10 VDC, impedance 100 kΩ only as alternative to 4-20 mA input, SELV

KL3

4

+10 V

Voltage output 10 VDC (+/-3%), max. 10 mA, supply voltage for ext. devices
(e.g. potentiometer), SELV

KL3

5

+20 V

Voltage output 20 VDC (+25%/-10%), max. 50 mA, supply voltage for ext. devices
(e.g. sensors), SELV

KL3

6

4-20 mA

Use control / actual value input 4-20 mA, impedance 100 Ω, only as alternative to 0-10 V input, SELV

KL3

9, 11

RSB

RS485 interface for ebmBus, RSB, SELV

KL3

10, 12

RSA

RS485 interface for ebmBus, RSA, SELV

Item no. 50167-5-9970 · Revision 82542 · Release 2014-05-08 · Page 9 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание R3G400-AM56-11

Страница 1: ...sts are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the...

Страница 2: ...rotor and impeller can be injured Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill DANGER Flying parts Missing safety d...

Страница 3: ...imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustaining or lifesaving function Operation with external vibrations Moving solids content in flow medium Pai...

Страница 4: ...476 2 4013 not included in the standard scope of delivery 2 Depth of screw max 16 mm 3 Cable diameter min 4 mm max 10 mm tightening torque 2 5 0 4 Nm 4 Tightening torque 3 5 0 5 Nm Item no 50167 5 997...

Страница 5: ...otor side Operation mode S1 Motor bearing Ball bearing Technical features Output 10 VDC max 10 mA Output 20 VDC max 50 mA Output for slave 0 10 V Input for sensor 0 10 V or 4 20 mA Alarm relay Integra...

Страница 6: ...ments for voltage current insulation material load etc Route cables such that they cannot be touched by any rotating parts DANGER Electrical load 50 C between mains wire and protective earth connectio...

Страница 7: ...ent operated device Only universal type B or B RCD protective devices are permitted Like frequency inverters RCD protective devices cannot provide personal safety while operating the device When switc...

Страница 8: ...e direction of the cable gland When routing the cable ensure that the screwed cable glands are arranged at the bottom The cables must always be routed downwards Fig 3 Cable routing for fans installed...

Страница 9: ...correspond to 100 level control coefficient KL3 2 8 GND Reference mass for control interface SELV KL3 3 7 0 10 V Use control actual value input 0 10 VDC impedance 100 k only as alternative to 4 20 mA...

Страница 10: ...re switching it on Check the air flow paths of the fan for foreign objects and remove any that are found Apply the nominal voltage to the voltage supply Start the device by changing the input signal 4...

Страница 11: ...ector responded Allow motor to cool off locate and rectify cause of error if necessary cancel restart lock out Overtemperature of electronics motor Insufficient cooling Improve cooling Let the device...

Страница 12: ...every 6 months Clean or replace impeller Tightness of screwed cable gland Visual inspection At least every 6 months Retighten replace if damaged Condensate discharge holes for clogging as necessary V...

Отзывы: