Operating instructions

R3G310-AX54-21

Translation of the original operating instructions

4.5 Connection screen

No.

Conn.

Designation

Function / assignment

KL1

1, 2

L1/N

Mains connection, power supply; see technical data for nominal voltage range

PE

PE

PE

Earth connection, PE connection

KL2

1

NO

Status relay, floating status contact, make for failure

KL2

2

COM

Status relay, floating status contact, changeover contact, common connection, contact rating, max. 250 VAC/2
A (AC1)/min. 10 mA

KL2

3

NC

Status relay, floating status contact, break for failure

KL3

1

RSA

Bus connection RS-485, RSA, MODBUS RTU; SELV

KL3

2

RSB

Bus connection RS-485, RSB, MODBUS RTU; SELV

KL3

3

GND

Signal ground for control interface, SELV

KL3

4

Ain1 U

Analogue input 1, set value: 0-10 V, Ri = 100 kΩ, parametrisable curve, only for use as alternative to input
Ain1; SELV

KL3

5

+10 V

Fixed voltage output 10 VDC, +10 V +/-3 %, max. 10 mA, short-circuit-proof, power supply for ext. devices
(e.g. potentiometer); SELV

KL3

6

Ain1 I

Analogue input 1, set value: 4-20 mA; Ri = 100 Ω, parametrisable curve, only for use as alternative to input
Ain1 U; SELV

KL3

7

Din1

Digital input 1: Enabling of electronics,
Enabling: Pin open or applied voltage 5-50 VDC
Disabling: Bridge to GND or applied voltage <1 VDC
Reset function: Triggers software reset after a level change to <1 VDC; SELV

KL3

8

Din2

Digital input 2: Parameter set 1/2 switching, depending on EEPROM setting, the valid/used parameter set can
be selected via the bus or via the digital input DIN2.
Parameter set 1: Pin open or applied voltage 5-50 VDC
Parameter set 2: bridge to GND or applied voltage <1 VDC; SELV

Item no. 50235-5-9970 · ENG · Revision 212555 · Release 2020-04-29 · Page 10 / 15

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание R3G310-AX54-21

Страница 1: ...e to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is...

Страница 2: ...mpliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Before working on the s...

Страница 3: ...Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibrations These also include vibrations that are transmitted from the customer system...

Страница 4: ...zle 31575 2 4013 not included in scope of delivery 2 Thread reach max 16 mm 3 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 4 Tightening torque 3 5 0 5 Nm Item no 50235 5 9970 ENG Revis...

Страница 5: ...ve the unit mm Inlet nozzle 31575 2 4013 with pressure tap not included in scope of delivery Item no 50235 5 9970 ENG Revision 212555 Release 2020 04 29 Page 5 15 ebm papst Mulfingen GmbH Co KG Bachm...

Страница 6: ...n with optimum efficiency The ErP data is determined using a motor impeller combination in a standardised measurement configuration 3 4 Technical features Mass 11 2 kg Size 310 mm Motor size 112 Surfa...

Страница 7: ...Make sure to avoid any shock Wear safety shoes and cut resistant safety gloves CAUTION Heavy load when taking out the device Bodily harm e g back injuries are possible Two people should remove the dev...

Страница 8: ...alues are typically in the range 250 mA At the same time the effective power in this operating state operational readiness is typically 4 W 4 2 3 Residual current operated device If the use of a resid...

Страница 9: ...n front of the cable gland for example When routing the cable ensure that the screwed cable glands are arranged at the bottom The cables must always be routed downwards Fig 3 Cable routing for fans in...

Страница 10: ...ive to input Ain1 SELV KL3 5 10 V Fixed voltage output 10 VDC 10 V 3 max 10 mA short circuit proof power supply for ext devices e g potentiometer SELV KL3 6 Ain1 I Analogue input 1 set value 4 20 mA R...

Страница 11: ...k parametrisable curve only usable as alternative to input Ain2 SELV KL3 12 20 V Fixed voltage output 20 VDC 20 V 25 10 max 50 mA short circuit proof power supply for ext devices e g sensors SELV Alte...

Страница 12: ...determine the speed ranges with excessive vibration levels and also any resonance frequencies that may be present When regulating the speed pass through resonance ranges as quickly as possible or fin...

Страница 13: ...during cleaning make sure to remove them afterwards Motor does not turn Mechanical blockage Switch off de energise and remove mechanical blockage Mains supply voltage faulty Check mains supply voltage...

Страница 14: ...r replacement of the device Check the device for damage to blades and housing Visual inspection At least every 6 months Replacement of the device Mounting the connection lines Visual inspection At lea...

Страница 15: ...external rotor motors from ebm papst Mulfingen GmbH Co KG Ferrite magnets can be disposed of in the same way as normal iron and steel Electrical insulating materials on the product in cables and wires...

Отзывы: