ebm-papst R3G310-AO52-01 Скачать руководство пользователя страница 8

Operating instructions

R3G310-AO52-01

Translation of the original operating instructions

4.5 Checking the connections

;

Make sure that the power is off (all phases).

;

Secure it from being switched on again.

;

Check the correct fit of the connection lines.

;

Route the connecting cables in the terminal box so that the terminal
box cover closes without resistance.

;

Use all plug screws (the entire number). In doing so, insert the
screws manually to avoid damage to the thread.

4.6 Switch on device

WARNING
Hot motor housing

Fire hazard
→ Ensure that no combustible or flammable materials are

located close to the fan.

;

Inspect the device for visible external damage and the proper function
of the protective features before switching it on.

;

Check the air flow paths of the fan for foreign objects and remove any
that are found.

;

Apply the nominal voltage to the voltage supply.

;

Start the device by changing the input signal.

4.7 Switching off the device

Switching off the device during operation:

;

Switch on the device via the control input.

;

Do not switch the motor (e.g. in cyclic operation) on and off via power
supply.

Switching off the device for maintenance work:

;

Switch on the device via the control input.

;

Do not switch the motor (e.g. in cyclic operation) on and off via power
supply.

;

Disconnect the device from the supply voltage.

;

When disconnecting, be sure to disconnect the earth wire connection
last.

5. INTEGRATED PROTECTIVE FUNCTIONS

The integrated protective functions cause the motor to switch off
automatically in case of faults described in the table.

Malfunctions

Description / Function of
safety feature

Rotor position detection error

An automatic restart occurs.

Locked rotor

;

After the blockage is

removed, the motor restarts
automatically.

Item no. 50944-5-9970 · Revision 72864 · Release 2011-02-18 · Page 8 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание R3G310-AO52-01

Страница 1: ...sonnel are permitted to transport unpack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the d...

Страница 2: ...ire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Befo...

Страница 3: ...the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving air that contains abrasive particles Moving highl...

Страница 4: ...ncluded in the standard scope of delivery other inlet nozzles on request 4 Depth of screw 8 10 mm tightening torque 2 5 0 2 Nm gluing the screws is recommended 5 Pilot hole prepared for self tapping s...

Страница 5: ...all bearing Technical features Output 10 VDC max 1 1 mA Tach output Motor current limit Soft start Control input 0 10 VDC PWM Over temperature protected electronics motor Touch current acc IEC 60990 m...

Страница 6: ...ing switch 4 2 1 Prerequisites Check whether the data on the type plate agree with the connection data Before connecting the device ensure that the supply voltage matches the operating voltage of the...

Страница 7: ...8 0 10 V PWM yellow Control input 0 10 V or PWM electrically isolated 9 Tach white Tach output open collector 1 pulse per revolution electrically isolated 11 10V max 1 1 mA red Voltage output 10 V ma...

Страница 8: ...e device by changing the input signal 4 7 Switching off the device Switching off the device during operation Switch on the device via the control input Do not switch the motor e g in cyclic operation...

Страница 9: ...tector responded Allow motor to cool off locate and rectify cause of error if necessary cancel restart lock out Overtemperature of electronics motor Insufficient cooling Improve cooling Let the device...

Страница 10: ...ge Visual inspection At least every 6 months Clean or replace impeller Check the ball bearings to ensure they are quiet can move easily and are free of play Manual check by turning the rotor in shut o...