Operating instructions

R3G280-RR05-N1

Translation of the original operating instructions

3. TECHNICAL DATA

3.1 Product drawing

All dimensions in mm.

1

Accessory part: Inlet ring 28004-2-4013 with pressure tap (k-factor: 77) not included in scope of delivery

2

Max. clearance for screw 16 mm

3

Cable, halogen-free, railway application EN 45545, 4G 1.5 mm²
4x wire-end ferrule

4

Cable, halogen-free, railway application EN 45545, 7x 0.5 mm²
7x wire-end ferrule

Item no. 55395-5-9970 · ENU · Change 257059 · Approved 2023-02-03 · Page 4 / 13

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание R3G280-RR05-N1

Страница 1: ...d by suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installatio...

Страница 2: ...customer equipment Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure t...

Страница 3: ...ing the operating instructions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt de...

Страница 4: ...ded in scope of delivery 2 Max clearance for screw 16 mm 3 Cable halogen free railway application EN 45545 4G 1 5 mm 4x wire end ferrule 4 Cable halogen free railway application EN 45545 7x 0 5 mm 7x...

Страница 5: ...s All dimensions in mm Inlet ring 28004 2 4013 with pressure tap k factor 77 Item no 55395 5 9970 ENU Change 257059 Approved 2023 02 03 Page 5 13 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mul...

Страница 6: ...circuit Fig 4 TN system 3 5 mA Motor protection Thermal overload protector TOP internally connected with cable Lateral Protection class I if protective earth is connected by customer to the housing s...

Страница 7: ...cut resistant safety gloves NOTE Damage to the device from vibration Bearing damage shorter service life The fan must not be subjected to force or excessive vibration from sections of the installation...

Страница 8: ...e 480 V 4 2 3 Reactive currents Because of the EMC filter integrated for compliance with EMC limits interference emission and immunity to interference reactive currents can be measured in the supply l...

Страница 9: ...NC orange Status relay floating status contact break for failure contact rating 250 VAC max 2 A AC1 min 1 mA 5 VDC reinforced insulation on control interface side basic insulation on supply side acco...

Страница 10: ...issible vibration severity must not exceed 3 5 mm s and should be checked at intervals of 6 months It is to be determined at the motor mount at the motor support plate at least in axial direction and...

Страница 11: ...y Device restarts automatically without warning Faulty connection Isolate from supply correct connection see connection diagram Broken motor winding Replace device Thermal overload protector activated...

Страница 12: ...er for wear deposits corrosion and damage Visual inspection At least every 6 months Clean impeller or replace device Condensation drainage holes for clogging where necessary Visual inspection At least...

Страница 13: ...aterials and are therefore to be treated in the same manner The materials concerned are as follows Miscellaneous insulators used in the terminal box Power cables Cables for internal wiring Electrolyti...

Отзывы: