ebm-papst R3G250-RE09-07 Скачать руководство пользователя страница 9

Operating instructions

R3G250-RE09-07

Translation of the original operating instructions

6. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES

Do not perform any repairs on your device. Return the device to ebm-
papst for repair or replacement.

WARNING
Terminals and connections have voltage even with a
unit that is shut off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

CAUTION
If control voltage is applied or a speed setpoint is stored,
the motor automatically restarts, e.g. after a power failure.

Danger of injury
→ Keep out of the danger zone of the device.
→ When working on the device, switch off the mains

supply voltage and secure the latter from being switched on
again.

→ Wait until the device stops.
→ After working on the device, remove any used tools or

other objects from the device.

If the device remains out of use for some time, e.g. when in
storage, we recommend switching the device on for at least
two hours to allow any condensate to evaporate and to move
the bearings.

Malfunction/error

Possible cause

Possible remedy

Impeller running
roughly

Imbalance in rotating
parts

Clean the device; if
imbalance is still
evident after
cleaning, replace the
device.
If you have
attached any weight
clips during cleaning,
make sure to
remove them
afterwards.

Motor does not turn

Mechanical blockage

Switch off, de-
energise, and
remove mechanical
blockage.

Mains supply
voltage faulty

Check mains supply
voltage,
restore power
supply,
apply control signal.

Faulty connection

De-energise, correct
connection, see
connection diagram.

Overtemperature of
electronics/motor

Insufficient cooling

Improve cooling. Let
the device cool
down.
To reset the error
message, switch off
the mains supply
voltage for a min. of
25 s and switch it on
again.

Ambient temperature
too high

Reduce the ambient
temperature.
Reset by reducing
control input to 0.

Unacceptable
operating point

Correct the operating
point. Let the device
cool down.

If you have any other problems, contact ebm-papst.

6.1 Cleaning

NOTE
Damage to the device during cleaning.

Malfunction possible
→ Do not clean the device using a water jet or high-pressure

washer.

→ Do not use any cleaners containing acids,

bases or solvents.

→ Do not use any pointed or sharp-edged objects to clean.

6.2 Safety test

NOTE
High-voltage test

The integrated EMC filter contains Y capacitors. Therefore, the
trigger current is exceeded when AC testing voltage is applied.
→ Test the device with DC voltage when you carry out the

high-voltage test required by law. The voltage to be used
corresponds to the peak value of the AC voltage required by
the standard.

What has to
be tested?

How to test?

Frequency

Which
measure?

Check the
protective
casing against
accidental
contact for
damage and to
ensure that it is
intact

Visual inspection At least every

6 months

Repair or
replacement of
the device

Check the
device for
damage to
blades and
housing

Visual inspection At least every

6 months

Replacement
of the device

Mounting the
connection lines

Visual inspection At least every

6 months

Fasten

Item no. 51152-5-9970 · Revision 75542 · Release 2012-11-06 · Page 9 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание R3G250-RE09-07

Страница 1: ...sed specialist personnel are permitted to transport unpack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards s...

Страница 2: ...ire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Befo...

Страница 3: ...the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving air that contains abrasive particles Moving highl...

Страница 4: ...n the standard scope of delivery 2 Connection line PVC 4X 0 5 mm 4 x brass lead tips crimped 3 Connection line PVC 3G 0 5 mm 3 x brass lead tips crimped 4 Depth of screw max 10 mm 5 Depth of screw max...

Страница 5: ...or on bottom rotor on top on request Condensate discharge holes None open rotor Operation mode S1 Motor bearing Ball bearing Technical features Output 10 VDC max 1 1 mA Tach output Motor current limit...

Страница 6: ...e device Only use cables designed for current according to the type plate For determining the cross section follow the basic principles in accordance with EN 61800 5 1 The protective earth must have a...

Страница 7: ...rth 1 GND blue GND Connection for control interface 2 0 10V PWM yellow Control input 0 10 V or PWM electrically isolated 3 10V max 1 1mA red Voltage output 10V 1 1mA electrically isolated not short ci...

Страница 8: ...e device by changing the input signal 4 7 Switching off the device Switching off the device during operation Switch on the device via the control input Do not switch the motor e g in cyclic operation...

Страница 9: ...ise correct connection see connection diagram Overtemperature of electronics motor Insufficient cooling Improve cooling Let the device cool down To reset the error message switch off the mains supply...

Страница 10: ...the wires for damage Visual inspection At least every 6 months Replace wires Impeller for wear deposits corrosion and damage Visual inspection At least every 6 months Clean or replace impeller Item n...

Страница 11: ...Mouser Electronics Authorized Distributor Click to View Pricing Inventory Delivery Lifecycle Information ebm papst R3G250 RE09 07...

Отзывы: