4. CONNECTION AND START-UP

4.1 Connecting the mechanical system

CAUTION
Cutting and crushing hazard when removing the fan
from the packaging

Carefully seize the impeller to lift the device out of its
packaging. Make sure to avoid any shock.

Wear safety shoes and cut-resistant safety gloves.

Check the device for transport damage. Damaged devices must no
longer be installed.

Install the undamaged device according to your application.

4.2 Connecting the electrical system

DANGER
Electric voltage on the device

Electric shock

Always install a protective earth.

Check the protective earth.

DANGER
Incorrect insulation

Risk of fatal injury from electric shock

Use only cables that meet the specified installation
requirements for voltage, current, insulation material, load etc.

Route cables such that they cannot touch any rotating
parts.

CAUTION
Electrical voltage

The fan is a built-in component and features no electrically
isolating switch.

Only connect the fan to circuits that can be switched off with
an all-pole separating switch.

When working on the fan, you must switch off the
installation/machine in which the fan is installed and secure it
from being switched on again.

NOTE
Water penetration into leads or wires

Water enters at the cable end on the customers side and can
damage the device.

Make sure that the cable end is connected in a dry
environment.

Connect the device only to circuits that can be switched off
using an all-pole disconnecting switch.

4.2.1 Prerequisites

Check whether the data on the type plate agree with the connection
data and the data of the operating capacitor.

Before connecting the device, ensure that the supply voltage matches
the operating voltage of the device.

Only use cables designed for current according to the type plate.

4.2.2 Voltage control

With open loop speed control using transformers or electronic
voltage regulators (e.g. phase angle control), excessive current
may occur.
In addition, noises can occur with phase angle control
depending on the mounting situation.

4.2.3 Frequency inverter

Fit sinusoidal filters that work on all poles (live-live and live-
earth) between the frequency inverter and the motor for
operation with frequency inverters.
Depending on how the device is installed, noises may occur.

4.3 Connection of the cables

External leads are brought out of device.

Connect the lines according to your application. When doing so,
observe chapter 4.4 Connection diagram.

Item no.: 10284-5-9970 · Revision status: KM73098 · Print-out on 01/02/2011 · Created by Y. Uhlmann (VM-TDO) · Page 6 of 9

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone: +49(0)7938/81-0 · Fax: +49(0)7938/81-110 · [email protected] · www.ebmpapst.com

Содержание R2E225-AT51-05

Страница 1: ...cal system Only trained and authorised specialist personnel are permitted to transport unpack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basi...

Страница 2: ...working on rotating parts Protect long hair by wearing a cap 1 7 Emission WARNING Depending on the installation and operating conditions a sound pressure level greater than 70 dB A may arise Danger o...

Страница 3: ...e operating instructions Improper use Using the device in the following ways is particularly prohibited and may cause hazards Moving air that contains abrasive particles Moving highly corrosive air e...

Страница 4: ...ped 2 Accessory part Inlet nozzle 96358 2 4013 not included in the standard scope of delivery 3 Screw depth max 5 mm 4 Direction of rotation clockwise seen on rotor Item no 10284 5 9970 Revision statu...

Страница 5: ...all bearing Mass 2 1 kg Material of impeller PA plastic 6 fibreglass reinforced Motor protection Thermal overload protector TOP wired internally Product conforming to standard CE EN 60335 1 Surface of...

Страница 6: ...tion into leads or wires Water enters at the cable end on the customers side and can damage the device Make sure that the cable end is connected in a dry environment Connect the device only to circuit...

Страница 7: ...n diagram U1 blue Z brown U2 black PE green yellow Item no 10284 5 9970 Revision status KM73098 Print out on 01 02 2011 Created by Y Uhlmann VM TDO Page 7 of 9 ebm papst Mulfingen GmbH Co KG Bachm hle...

Страница 8: ...he device CAUTION Electrical load on the capacitor after device is switched off Electric shock risk of injury Discharge the capacitors before working on the device CAUTION The motor restarts automatic...

Страница 9: ...tested How to test Frequency Protective casing against accidental contact Visual inspection at least every 6 months Device for damage Visual inspection at least every 6 months Mounting of device Visu...

Отзывы: