ebm-papst R2E150-AN91-05 Скачать руководство пользователя страница 9

Operating instructions

R2E150-AN91-05

Translation of the original operating instructions

Unacceptable
operating point

Check operating point

Overtemperature of
motor

Ambient temperature
too high

Lower ambient
temperature if possible

Insufficient cooling

Improve cooling

If you have any other problems, contact ebm-papst.

5.1 Cleaning

NOTE
Damage to the device during cleaning.

Malfunction possible
→ Do not clean the device using a water jet or high-pressure

washer.

→ Do not use any cleaners containing acids,

bases or solvents.

→ Do not use any pointed or sharp-edged objects to clean.

5.2 Safety test

What has to
be tested?

How to test?

Frequency

Which
measure?

Check the
protective
casing against
accidental
contact for
damage and to
ensure that it is
intact

Visual inspection At least every

6 months

Repair or
replacement of
the device

Device for
damage

Visual inspection At least every

6 months

Replace device

Mounting the
connection lines

Visual inspection At least every

6 months

Fasten

Mounting of
protective
earth connection

Visual inspection At least every

6 months

Fasten

Check the
insulation of
the wires for
damage

Visual inspection At least every

6 months

Replace wires

Weld seams
for crack
formation

Visual inspection At least every

6 months

Replace device

Check the ball
bearings to
ensure they
are quiet, can
move easily
and are free of
play

Manual check
by turning the
rotor in shut-off
state

At least every
6 months

Replace
device in case
of noise,
difficulty of
movement or
clearance of
the bearings

Item no. 10691-5-9970 · Revision 68158 · Release 2012-02-22 · Page 9 / 9

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание R2E150-AN91-05

Страница 1: ...stem Only trained and authorised specialist personnel are permitted to transport unpack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic safe...

Страница 2: ...could become entangled and pulled into the device You could be injured Do not wear any loose clothing or jewellery while working on rotating parts Protect long hair by wearing a cap 1 7 Emission WARNI...

Страница 3: ...es in place Minding the operating instructions Improper use Using the device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by...

Страница 4: ...measures have the unit mm 1 Connection line silicone 4x brass lead tips crimped 2 Connection line 3x brass lead tips crimped Item no 10691 5 9970 Revision 68158 Release 2012 02 22 Page 4 9 ebm papst M...

Страница 5: ...bearing Touch current acc IEC 60990 measuring network Fig 4 TN system 0 75 mA Motor protection Thermal overload protector TOP wired internally Cable exit Variable Protection class I if protective eart...

Страница 6: ...n all pole disconnecting switch 4 2 1 Prerequisites Check whether the data on the type plate agree with the connection data and the data of the operating capacitor Before connecting the device ensure...

Страница 7: ...on diagram U1 blue Z brown U2 black PE green yellow 2 Hall IC circuit 2 1 Hall IC 2 2 red 5V 2 3 white out 2 4 black 0V Item no 10691 5 9970 Revision 68158 Release 2012 02 22 Page 7 9 ebm papst Mulfin...

Страница 8: ...off Electric shock risk of injury Discharge the capacitors before working on the device CAUTION The motor restarts automatically when operating voltage is applied e g after a power failure Danger of i...

Страница 9: ...nspection At least every 6 months Repair or replacement of the device Device for damage Visual inspection At least every 6 months Replace device Mounting the connection lines Visual inspection At leas...

Отзывы: