Operating instructions

R1G175-AE73-10

Translation of the original operating instructions

4. CONNECTION AND STARTUP

4.1 Mechanical connection

CAUTION
Cutting and crushing hazard when removing fan from
packaging

→ Carefully remove the device from its packaging, by the fan

impeller. Strictly avoid shocks.

→ Wear safety shoes and cut-resistant safety gloves.

NOTE
Damage to the device from vibration

Bearing damage, shorter service life
→ The fan must not be subjected to force or excessive vibration

from sections of the installation.

→ If the fan is connected to air ducts, the connection should

be isolated from vibration, e.g. using compensators or similar
elements.

→ Ensure stress-free attachment of the fan to the

substructure.

;

Check the device for transport damage. Damaged devices are not to
be installed.

;

Install the undamaged device in accordance with your application.

CAUTION
Possible damage to the device

If the device slips during installation, serious damage can result.
→ Ensure that the device is securely positioned at its place of

installation until all fastening screws have been tightened.

The fan must not be strained on fastening.

4.2 Electrical connection

CAUTION
Voltage

The fan is a built-in component and has no disconnecting switch.
→ Only connect the fan to circuits that can be switched off with

an all-pole disconnection switch.

→ When working on the fan, secure the system/machine in

which the fan is installed so as to prevent it from being
switched back on.

NOTE
Water ingress into wires or cables

Water ingress at the customer end of the cable can damage the
device.
→ Make sure the end of the cable is connected in a dry

environment.

4.2.1 Requirements

;

Check whether the information on the nameplate matches the
connection data.

;

Before connecting the device, make sure the power supply matches
the device voltage.

;

Only use cables designed for the current level indicated on the
nameplate.
For determining the cross-section, note the sizing criteria according
to EN 61800-5-1. The protective earth must have a cross-section
equal to or greater than that of the phase conductor.
We recommend the use of 105 °C cables. Ensure that the minimum

cable cross-section is at least
AWG 26 / 0.13 mm².

Operate the device with a safely isolated power supply.

4.3 Plug connection

4.3.1 Making supply connections

;

Check your connector's pin assignment.

;

Connect the built-in connector with the mating connector.

;

Ensure that the connector is properly engaged.

Item no. 54899-5-9970 · ENU · Change 237649 · Approved 2022-09-06 · Page 6 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание R1G175-AE73-10

Страница 1: ...packed installed operated maintained and otherwise used by suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test...

Страница 2: ...vement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor and the impeller Secure the device to prevent contact Before working on the system machine wait until all...

Страница 3: ...hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fan...

Страница 4: ...e of delivery 2 Max clearance for screw 6 mm 3 Cable PVC AWG20 4 pole connector housing Molex 39 01 2045 4x socket Molex 39 00 0059 3 1 UN 48 VDC red 3 2 PWM LIN yellow 3 3 Tach white 3 4 GND blue Ite...

Страница 5: ...standards EN 62368 1 Approval CSA C22 2 No 100 UL 1004 1 With regard to cyclic speed loads note that the rotating parts of the device are designed for a maximum of one million load cycles If you have...

Страница 6: ...ecting switch Only connect the fan to circuits that can be switched off with an all pole disconnection switch When working on the fan secure the system machine in which the fan is installed so as to p...

Страница 7: ...red Power supply 48 VDC maximum ripple 3 5 1 2 0 10 VDC yellow Control input Re 100k 1 3 Tach white Tach output 3 pulses per revolution Isink max 10 mA 1 4 GND blue Reference ground Item no 54899 5 99...

Страница 8: ...enance Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the power supply 5 MAINTENANCE MALFUNCTIONS PO...

Страница 9: ...very 6 months Clean impeller or replace device Condensation drainage holes for clogging where necessary Visual inspection At least every 6 months Open holes Abnormal bearing noise acoustic At least ev...

Страница 10: ...s Miscellaneous insulators used in the terminal box Power cables Cables for internal wiring Electrolytic capacitors Dispose of electronic components employing the proper procedures for electronic scra...