Operating instructions
K3G560-PC04-05
Translation of the original operating instructions
No.
Conn.
Designation
Function / assignment
KL 3
11
Ain2 U
Analogue input 2, actual value: 0-10 V, Ri = 100 kΩ, parametrisable curve, only usable as alternative to input
Ain2; SELV
KL 3
12
+ 20 V
Fixed voltage output 20 VDC, +20 V +25/-10%, max. 50 mA, short-circuit-proof, power supply for ext.
devices (e.g. sensors); SELV
Alternatively: +24 VDC input for parametrisation without mains power
KL 3
13
Ain2 I
Analogue input 2, actual value: 4-20 mA, Ri = 100 Ω, parametrisable curve, only for use as alternative to input
Ain2 U; SELV
KL 3
14
Aout
Analogue output 0-10 V, max. 5 mA, output of current motor level control coefficient; parametrisable curve; SELV
Item no. 55162-5-9970 · ENG · Revision 202992 · Release 2019-03-13 · Page 11 / 15