background image

Operating instructions

K3G560-AQ04-01

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G150-NA

Phase

3~

Nominal voltage / VAC

400

Nominal voltage
range / VAC

380 .. 480

Frequency / Hz

50/60

Type of data definition

ml

Speed / min

-1

1750

Power input / W

4700

Current draw / A

7.3

Min. ambient temperature
/ °C

-25

Max. ambient
temperature
/ °C

40

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Data according to ErP directive

Installation category

A

Efficiency category

Static

Variable speed drive

Yes

Specific ratio

*

1.01

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Actual

Request
2013

Request
2015

Overall efficiency η

es

/ %

67.2

54.5

58.5

Efficiency grade N

70.7

58

62

Power input P

ed

/ kW

4.67

Air flow q

v

/ m³/h

11640

Pressure increase total p

sf

/ Pa

934

Speed n / min

-1

1765

Data definition with optimum efficiency.

The ErP data is determined using a motor-impeller combination in a standardised

measurement configuration.

3.4 Technical features

Mass

69 kg

Size

560 mm

Surface of rotor

Coated in black

Material of electronics
housing

Die-cast aluminium

Material of impeller

Aluminium sheet

Material of mounting
plate

Sheet steel, galvanised

Material of support
bracket

Steel, coated in black

Material of inlet nozzle

Sheet steel, galvanised

Number of blades

7

Direction of rotation

Clockwise, seen on rotor

Type of protection

IP 54

Insulation class

"F"

Humidity class

F4-1

Mounting position

Shaft horizontal or rotor on bottom

Condensate discharge
holes

Rotor-side

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA
- Output for slave 0-10 V
- Operation and alarm display
- Input for sensor 0-10 V or 4-20 mA
- External 24 V input (programming)
- External release input
- Alarm relay
- Integrated PID controller
- Motor current limit
- PFC, passive
- RS485 MODBUS RTU
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Over-temperature protected
electronics / motor
- Line undervoltage / phase failure
detection

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical leads

Via terminal box

Motor protection

Reverse polarity and locked-rotor
protection

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 61800-5-1; CE

Approval

C22.2 Nr.77 + CAN/CSA-E60730-1;
EAC; UL 1004-7 + 60730

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.5 Mounting data

;

Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

3.6 Transport and storage conditions

;

Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+80 °C

Min. permissible
ambient motor temp.
(transp./storage)

-40 °C

Item no. 50978-5-9970 · ENG · Revision 82549 · Release 2014-05-08 · Page 5 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3G560-AQ04-01

Страница 1: ...to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is...

Страница 2: ...on the system machine wait until all parts have come to a standstill DANGER Flying parts Missing safety devices may cause balancing weights or broken fan blades to be ejected at high speeds causing bo...

Страница 3: ...ce in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustain...

Страница 4: ...ning torque 4 0 6 Nm 2 Cable diameter min 9 mm max 16 mm tightening torque 6 0 9 Nm 3 Inlet nozzle with bleeder connection for pressure relief k factor 348 4 Tightening torque 3 5 0 5 Nm Item no 50978...

Страница 5: ...r side Operation mode S1 Motor bearing Ball bearing Technical features Output 10 VDC max 10 mA Output 20 VDC max 50 mA Output for slave 0 10 V Operation and alarm display Input for sensor 0 10 V or 4...

Страница 6: ...nger be installed Install the undamaged device according to your application 4 2 Connecting the electrical system DANGER Electric voltage on the device Electric shock Always install a protective earth...

Страница 7: ...AC 16 A 15 A C16A 1 5 16 3 PE AC 380 480 VAC 20 A 20 A C20A 2 5 14 3 PE AC 380 480 VAC 25 A 25 A C25A 4 0 12 3 PE AC 380 480 VAC 32 A 30 A C32A 6 0 10 AWG American Wire Gauge 4 2 3 Idle current Becaus...

Страница 8: ...at no cables splice off Fig 2 Connecting the wires to terminals Seal the terminal box 4 3 3 Cable routing No water may penetrate along the cable in the direction of the cable gland When routing the ca...

Страница 9: ...n pin or applied voltage 5 50 VDC disabling bridge to GND or applied voltage 1 VDC reset function triggers software reset after a level change to 1 VDC SELV KL 3 8 Din2 Digital input 2 parameter set s...

Страница 10: ...fan for foreign objects and remove any that are found Apply the nominal voltage to the voltage supply Start the device by changing the input signal 4 8 Switching off the device Switching off the devi...

Страница 11: ...Switch off de energise and remove mechanical blockage Mains supply voltage faulty Check mains supply voltage restore power supply Important The error message resets automatically The device starts up...

Страница 12: ...nst accidental contact for damage and to ensure that it is intact Visual inspection At least every 6 months Repair or replacement of the device Check the device for damage to blades and housing Visual...