Operating instructions

K3G500-RA28-03

Translation of the original operating instructions

Approval

UL 1004-7 + 60730-1; EAC; CSA
C22.2 No. 77 + CAN/CSA-E60730-1

Comment

Maximum permissible operating altitude
4000 m above sea level according to
DIN 61800-5-1_2008_Sec. 4.3.6.4.1
overvoltage category II.
Up to 2000 m above sea level,
overvoltage category III applies.

;

Use the device in accordance with its degree of protection.

Information on surface quality

The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may change during the production period.
This has no effect on strength, dimensional stability and dimensional
accuracy.
The color pigments in the paints used perceptibly react to UV light over
the course of time. The product is to be protected against UV radiation to
prevent the formation of patches and fading. Changes in color are not a
reason for complaint and are not covered by the warranty. UV radiation
in the frequency range and the intensity of natural solar radiation has no
effect on the technical properties of the products.

3.5 Mounting data

Further mounting data can be taken from the product drawing or Chapter
4.1 Mechanical connection as required.

Strength class of
screws

8.8

;

Secure the screws against unintentional loosening (e.g. use self-
locking screws).

3.6 Transport and storage conditions

Max. permitted
ambient temp. for
motor (transport/
storage)

+80 °C

Min. permitted
ambient temp. for
motor (transport/
storage)

-40 °C

3.7 Electromagnetic compatibility

EMC immunity to
interference

According to EN 61000-6-2 (industrial
environment)

EMC interference
emission

According to EN 61000-6-3 (household
environment), except EN 61000-3-2 for
professionally used equipment with a
total rated power greater than 1 kW

If several devices are connected in parallel on the supply side
so that the line current of the arrangement is in the range 16 - 75
A, this arrangement conforms to IEC 61000-3-12, provided that
the short-circuit power S

sc at the connection point of the

customer system to the public power grid is greater than or
equal to 250 times the rated output of the arrangement. It is the
responsibility of the installation engineer or operator/owner of the
device to ensure, if necessary after consultation with the
network operator, that this device is only connected to a
connection point with an S

sc value greater than or equal to 250

times the rated output of the arrangement.

4. CONNECTION AND STARTUP

4.1 Mechanical connection

CAUTION
Risk of cutting and crushing when removing device
from packaging

→ Carefully remove the device from the packaging by grasping

hold of the frame. Never subject to any impact.

→ Wear safety shoes and cut-resistant safety gloves.

CAUTION
Device weighs over 25 kg! Heavy load when unpacking
device.

Risk of physical injury, such as back injuries.
→ Use suitable hoisting equipment to remove the device from

its packaging.

NOTE
Damage to the device from vibration

Bearing damage, shorter service life
→ The fan must not be subjected to force or excessive vibration

from sections of the installation.

→ If the fan is connected to air ducts, the connection should

be isolated from vibration, e.g. using compensators or similar
elements.

→ Ensure stress-free attachment of the fan to the

substructure.

;

The fan may not be handled in the area around the inlet nozzle during
transport and installation.
There is a risk of damage to the impeller.

;

Check the device for transport damage. Damaged devices are not to
be installed.

;

Install the undamaged device in accordance with your application.

CAUTION
Possible damage to the device

If the device slips during installation, serious damage can result.
→ Ensure that the device is securely positioned at its place of

installation until all fastening screws have been tightened.

The fan must not be strained on fastening.

4.2 Electrical connection

DANGER
Voltage on the device

Electric shock
→ Always connect a protective earth first.
→ Check the protective earth.

DANGER
Faulty insulation

Risk of fatal injury from electric shock
→ Use only cables that meet the specified installation

regulations for voltage, current, insulation material, capacity,
etc.

→ Route cables so that they cannot be touched by any

rotating parts.

Item no. 55741-5-9970 · ENU · Change 260717 · Approved 2022-06-23 · Page 6 / 16

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3G500-RA28-03

Страница 1: ... a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation in the final product The locally applicable industrial safety regulations are always to be observed when working on the device Keep the workplace clean and tidy Untidiness in the work area increase...

Страница 2: ...fore working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be ejected and cause injuries Take appropriate safety measures WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become entangled and be pulled into the device Injuries can resul...

Страница 3: ...3 6 Transport and storage conditions and Chapter 3 2 Nominal data Operating the device with all protective devices Following the operating instructions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This...

Страница 4: ...x 10 mm tightening torque 4 0 6 Nm The tightening torque is designed for PVC cables If the cable materials are different the tightening torque may have to be adjusted 3 Tightening torque 1 5 0 2 Nm 4 Attachment holes for FlowGrid 35505 2 2957 not included in scope of delivery Item no 55741 5 9970 ENU Change 260717 Approved 2022 06 23 Page 4 16 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mul...

Страница 5: ...ensions must be requested from ebm papst If other air conduction geometries are used on the installation side the ebm papst evaluation loses its validity the conformity must be confirmed again The product does not fall within the scope of Regulation EU 2019 1781 due to the exception specified in Article 2 2a motors completely integrated into a product 3 4 Technical description Weight 35 kg Size 50...

Страница 6: ...tput of the arrangement It is the responsibility of the installation engineer or operator owner of the device to ensure if necessary after consultation with the network operator that this device is only connected to a connection point with an Ssc value greater than or equal to 250 times the rated output of the arrangement 4 CONNECTION AND STARTUP 4 1 Mechanical connection CAUTION Risk of cutting a...

Страница 7: ...e necessary to connect an additional protective earth conductor by way of the extra protective earth terminal provided on the device The protective earth terminal is located on the housing and provided with a protective earth symbol and a hole 4 2 2 Supply connection and fuses Assignment of supply cable cross sections and their required fuses line protection only no equipment protection Nominal vo...

Страница 8: ... of the drive and the type of cable routing see Chapter 4 2 2 Supply connection and fuses Control and relay cables min max Rigid cable cross section 0 2 mm 1 5 mm Flexible cable cross section 0 2 mm 1 5 mm AWG kcmil cable cross section 24 16 Wire end ferrules with insulating collar in accordance with DIN 46228 4 for flexible cable 0 14 mm 0 75 mm Wire end ferrules without insulating collar in acco...

Страница 9: ...ust be provided with strain relief The cable glands must be tight Fit the terminal box cover making sure that the sealing surfaces are clean Screw in the four screws for tightening torque see Chapter 3 1 Product drawing 4 3 4 Cable routing Water must be prevented from reaching the cable gland along the cable NOTE Damage caused by moisture penetration Moisture can penetrate into the terminal box if...

Страница 10: ...teristic curve P1 IN SELV CON2 IO3 Function parameterizable see Optional interface functions table Factory setting Analog output 0 10 V max 5 mA function Fan modulation level Characteristic curve parameterizable see output characteristic curve P3 OUT SELV CON2 Vout Voltage output 3 3 24 VDC 5 Pmax 800 mW voltage parameterizable Factory setting 10 VDC short circuit proof supply for external devices...

Страница 11: ...D159 0 Ain2 0 10V PWM analog input D159 2 Ri 100K characteristic curve parameterizable f PWM 1k 10KHz SELV Ain2 4 20mA analog input Ri 125R characteristic curve parameterizable SELV D159 3 Din3 active high digital input not active pin open or applied voltage 1 5VDC active applied voltage 3 5 50VDC SELV D15A 0 Din3 active low digital input not active pin open or applied voltage 3 5 50VDC active app...

Страница 12: ... operating instructions 4 7 Equivalent circuit diagrams Item no 55741 5 9970 ENU Change 260717 Approved 2022 06 23 Page 12 16 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 13: ...ing Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with excessively high vibration levels can lead to premature failure The maximum permissible vibration severity must not exceed 3 5 mm s and should be checked at intervals of 6 months It is to be determined at the motor mount at the motor support plate at least in axial direction an...

Страница 14: ... automatically without warning Faulty connection Isolate from supply correct connection see connection diagram Broken motor winding Replace device Inadequate cooling Improve cooling Allow the device to cool down Ambient temperature too high Reduce the ambient temperature Allow the device to cool down Impermissible operating point e g back pressure too high Correct the operating point Allow the dev...

Страница 15: ...ensors depends on the device concerned and the installation situation 6 3 Cleaning To ensure a long service life check the fans regularly for proper operation and soiling The frequency of checking is to be adapted accordingly depending on the degree of soiling DANGER Risk of injury from rotating fan Only clean when not in motion Do not disconnect the fan from the power supply just switch it off vi...

Страница 16: ...ons for ecological disposal of the product and its components 6 5 1 Country specific legal requirements NOTE Country specific legal requirements Always observe the applicable country specific legal regulations with regard to the disposal of products or waste occurring in the various phases of the life cycle The corresponding disposal standards are also to be heeded 6 5 2 Disassembly Disassembly of...

Отзывы: