Operating instructions

K3G450-AZ30-01

Translation of the original operating instructions

No.

Conn.

Designation

Function / assignment

KL 3

6

Ain1 I

Analogue input 1, set value: 4-20 mA; Ri = 100 Ω, parametrisable curve, only for use as alternative to input
Ain1 U; SELV

KL 3

7

Din1

Digital input 1: Enabling of electronics,
Enabling: Pin open or applied voltage 5-50 VDC
Disabling: Bridge to GND or applied voltage <1 VDC
Reset function: Triggers software reset after a level change to <1 VDC; SELV

KL 3

8

Din2

Digital input 2: Parameter set 1/2 switching, depending on EEPROM setting, the valid/used parameter set can
be selected via the bus or via the digital input DIN2.
Parameter set 1: Pin open or applied voltage 5-50 VDC
Parameter set 2: bridge to GND or applied voltage <1 VDC; SELV

KL 3

9

Din3

Digital input 3: Controller function of integrated controller; depending on EEPROM setting, normal / inverse can
be selected for the controller function of the integrated controller via the bus or the digital input
Normal: Pin open or applied voltage 5-50 VDC
Inverse: bridge to GND or applied voltage <1 VDC; SELV

KL 3

11

Ain2 U

Analogue input 2, actual value: 0-10 V, Ri = 100 kΩ, parametrisable curve, only usable as alternative to input
Ain2; SELV

KL 3

12

+ 20 V

Fixed voltage output 20 VDC, +20 V +25/-10%, max. 50 mA, short-circuit-proof, power supply for ext.
devices (e.g. sensors); SELV
Alternatively: +24 VDC input for parametrisation without mains power

KL 3

13

Ain2 I

Analogue input 2, actual value: 4-20 mA, Ri = 100 Ω, parametrisable curve, only for use as alternative to input
Ain2 U; SELV

KL 3

14

Aout

Analogue output 0-10 V, max. 5 mA, output of current motor level control coefficient; parametrisable curve; SELV

Item no. 50864-5-9970 · ENG · Revision 209539 · Release 2021-02-12 · Page 11 / 15

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3G450-AZ30-01

Страница 1: ...ry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is install...

Страница 2: ...Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill DANGER Flying parts Missing safety devices may cause balancing weights...

Страница 3: ...r 3 2 Nominal data Operating the device with all protective features in place Minding the operating instructions Improper use Using the device in the following ways is particularly prohibited and may...

Страница 4: ...10 mm tightening torque 4 0 6 Nm 2 Cable diameter min 9 mm max 16 mm tightening torque 6 0 9 Nm 3 Inlet nozzle with pressure tap k factor 240 4 Tightening torque 3 5 0 5 Nm Item no 50864 5 9970 ENG R...

Страница 5: ...installation side the ebm papst evaluation loses its validity conformity must be confirmed again The product does not fall within the scope of Regulation EU 2019 1781 due to the exception specified i...

Страница 6: ...ator owner of the device to ensure if necessary after consultation with the network operator that this device is only connected to a connection point with a Ssc value that is greater than or equal to...

Страница 7: ...ter enters at the cable end on the customers side and can damage the device Make sure that the cable end is connected in a dry environment Connect the device only to circuits that can be switched off...

Страница 8: ...protection Due to the locked rotor protection the start up current LRA is equal to or less than the nominal current FLA 4 3 Connection in terminal box 4 3 1 Preparing connection lines for the connect...

Страница 9: ...example When routing the cable ensure that the screwed cable glands are arranged at the bottom The cables must always be routed downwards Fig 4 Cable routing for fans installed upright 4 4 Factory set...

Страница 10: ...common connection contact rating max 250 VAC 2 A AC1 min 10 mA KL 2 3 NC Status relay floating status contact break for failure KL 3 1 RSA Bus connection RS485 RSA MODBUS RTU SELV KL 3 2 RSB Bus conn...

Страница 11: ...depending on EEPROM setting normal inverse can be selected for the controller function of the integrated controller via the bus or the digital input Normal Pin open or applied voltage 5 50 VDC Invers...

Страница 12: ...nce frequencies that may be present When regulating the speed pass through resonance ranges as quickly as possible or find another remedy Operation at excessive vibration levels can lead to premature...

Страница 13: ...f de energise and remove mechanical blockage Mains supply voltage faulty Check mains supply voltage restore power supply Important The error message resets automatically The device starts up again aut...

Страница 14: ...with maintenance free ball bearings The lifetime lubrication of the ball bearings is designed for a service life of 40 000 hours Please contact ebm papst if bearing replacement is required after this...

Страница 15: ...ts could drop off during disassembly This can result in fatal or serious injury and material damage Secure components before unfastening to stop them falling 6 4 3 Component disposal The products are...

Отзывы: