ebm-papst K3G400-RJ75-01 Скачать руководство пользователя страница 9

Operating instructions

K3G400-RJ75-01

Translation of the original operating instructions

4.5 Connection diagram

Drawing preliminary!

No.

Conn.

Designation

Color

Function/assignment

1

1, 2

PE

green/
yellow

Protective earth

1

3

L1

black

Power supply

1

4

L2

black

Power supply

1

5

L3

black

Power supply

1

6

NC

white 1

Status relay, floating status contact, break for failure,
contact rating 250 VAC / 2 A (AC1) / min. 10 mA; reinforced insulation on supply side and basic
insulation on control interface side

1

7

COM

white 2

Status relay, floating status contact, break for failure,
contact rating 250 VAC / 2 A (AC1) / min. 10 mA; reinforced insulation on supply side and basic
insulation on control interface side

2

8

0-10V

yellow

Analog input (set value), 0-10 V, Ri = 100 kΩ, adjustable curve, SELV

2

10

RSB

brown

RS485 interface for MODBUS, RSB; SELV

2

11

RSA

white

RS485 interface for MODBUS, RSA; SELV

2

12

GND

blue

Reference ground for control interface, SELV

2

13

+10V

red

Fixed voltage output 10 VDC, +10 V ±3%, max. 10 mA, short-circuit-proof power supply for
external devices (e.g. pot), SELV
fixed voltage input 24 VDC for setting parameters via MODBUS without line voltage supply

Item no. 52546-5-9970 · ENU · Change 212422 · Approved 2020-07-14 · Page 9 / 13

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3G400-RJ75-01

Страница 1: ...are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the de...

Страница 2: ...ore working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be ejected and caus...

Страница 3: ...2 Nominal data Operating the device with all protective devices Following the operating instructions Improper use In particular operating the device in the following ways is prohibited and could be h...

Страница 4: ...install support struts only vertically as illustrated or rotor on bottom rotor on top on request 2 Cable PVC AWG18 6x crimped ferrules 3 Cable PVC AWG22 5x crimped ferrules Item no 52546 5 9970 ENU C...

Страница 5: ...using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 16 5 kg Size 400 mm Motor size 112 Rotor surface Painted black Electronics housing material Die...

Страница 6: ...blic power grid is greater than or equal to 250 times the rated output of the arrangement It is the responsibility of the installation engineer or operator owner of the device to ensure if necessary a...

Страница 7: ...necessary to connect an additional protective earth conductor by way of the extra protective earth terminal provided on the device The protective earth terminal is located on the housing and provided...

Страница 8: ...ade for the device by ebm papst Mode parameter set 1 PWM control Mode parameter set 2 PWM control Fan device address 01 Max PWM 100 Min PWM 5 Save set value to EEPROM Yes Set value requirement Analog...

Страница 9: ...g 250 VAC 2 A AC1 min 10 mA reinforced insulation on supply side and basic insulation on control interface side 2 8 0 10V yellow Analog input set value 0 10 V Ri 100 k adjustable curve SELV 2 10 RSB b...

Страница 10: ...issible vibration severity must not exceed 3 5 mm s and should be checked at intervals of 6 months It is to be determined at the motor mount at the motor support plate at least in axial direction and...

Страница 11: ...eck line voltage restore power supply Attention The error message resets automatically Device restarts automatically without warning Faulty connection Isolate from supply correct connection see connec...

Страница 12: ...after that period contact ebm papst Adapt the maintenance intervals to the actual level of dust exposure 6 3 Safety inspection NOTE High voltage test The integrated EMC filter has Y capacitors The tr...