4.5 Checking the connections

; Make sure that the power is off (all phases).
; Secure it from being switched on again.
; Check the correct fit of the connection lines.

4.6 Switch on device

The device may only be switched on if it has been installed properly and
in accordance with its intended use, including the required safety
mechanisms and professional electrical connection. This also applies for
devices which have already been equipped with plugs and terminals or
similar connectors by the customer.

WARNING

Hot motor housing

Fire hazard
→ Ensure that no combustible or flammable materials are

located close to the fan.

; Inspect the device for visible external damage and the proper function

of the protective features before switching it on.

; Check the air flow paths of the fan for foreign objects and remove any

that are found.

; Apply the nominal voltage to the voltage supply.
; Start the device by changing the input signal.

4.7 Switching off the device

Switching off the device during operation:
; Switch off the device via the control input.
; Do not switch the motor (e.g. in cyclic operation) on and off via power

supply.

Switching off the device for maintenance work:
; Switch off the device via the control input.
; Do not switch the motor (e.g. in cyclic operation) on and off via power

supply.

; Disconnect the device from the supply voltage.
; When disconnecting, be sure to disconnect the earth wire connection

last.

5. INTEGRATED PROTECTIVE FUNCTIONS

The integrated protective functions cause the motor to switch off
automatically in case of faults described in the table.

Malfunctions

Description / Function of
safety feature

Rotor position detection error

An automatic restart occurs.

Locked rotor

; After the blockage is
removed, the motor restarts
automatically.

Item no. 51762-5-9970 · Revision 80872 · Release 2013-07-08 · Page 8 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3G355-RB03-03

Страница 1: ...authorised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device Observe the following when working on the unit Do not make any modifications additions or conversions to the devic...

Страница 2: ...at the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair loose items of clothing and jewellery could become entangled and pulled into...

Страница 3: ... the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving air that contains abrasive particles Moving highly corrosive air e g salt spray mist Exceptions are devices that are intended for salt spray mist and protected accordingly Moving air that contains dust pollution e g suctioning off saw dust Operatin...

Страница 4: ...easures have the unit mm 1 Connection line AWG20 3x brass lead tips crimped 2 Connection line AWG22 4x brass lead tips crimped Item no 51762 5 9970 Revision 80872 Release 2013 07 08 Page 4 10 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 5: ...r Type of protection IP 54 Insulation class B Humidity class F3 1 Mounting position Any Condensate discharge holes None open rotor Cooling bore aperture Rotor side Operation mode S1 Motor bearing Ball bearing Technical features Output 10 VDC max 1 1 mA Tach output Motor current limit Soft start Control input 0 10 VDC PWM Over temperature protected electronics motor Touch current acc IEC 60990 meas...

Страница 6: ...4 2 1 Prerequisites Check whether the data on the type plate agree with the connection data Before connecting the device ensure that the supply voltage matches the operating voltage of the device Only use cables designed for current according to the type plate For determining the cross section follow the basic principles in accordance with EN 61800 5 1 The protective earth must have a cross sectio...

Страница 7: ...ue GND Connection for control interface 2 0 10V PWM yellow Control input 0 10 V or PWM electrically isolated 3 10V max 1 1mA red Voltage output 10 V 1 1 mA electrically isolated not short circuit proof Isink 10 mA 4 Tach white Tach output open collector 1 pulse per revolution electrically isolated Isink max 10 mA Item no 51762 5 9970 Revision 80872 Release 2013 07 08 Page 7 10 ebm papst Mulfingen ...

Страница 8: ... the nominal voltage to the voltage supply Start the device by changing the input signal 4 7 Switching off the device Switching off the device during operation Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Switching off the device for maintenance work Switch off the device via the control input Do not switch the motor e g in...

Страница 9: ...gise correct connection see connection diagram Overtemperature of electronics motor Insufficient cooling Improve cooling Let the device cool down To reset the error message switch off the mains supply voltage for a min of 25 s and switch it on again Ambient temperature too high Reduce the ambient temperature Reset by reducing control input to 0 Unacceptable operating point Correct the operating po...

Страница 10: ...f the wires for damage Visual inspection At least every 6 months Replace wires Impeller for wear deposits corrosion and damage Visual inspection At least every 6 months Clean or replace impeller Item no 51762 5 9970 Revision 80872 Release 2013 07 08 Page 10 10 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst c...

Отзывы: