ebm-papst K3G355-PH49-02 Скачать руководство пользователя страница 4

Operating instructions

K3G355-PH49-02

Translation of the original operating instructions

3. TECHNICAL DATA

3.1 Product drawing

All dimensions in mm.

1

Installed position: shaft horizontal (install support struts only vertically as illustrated) or rotor on bottom; rotor on top on request

2

Cable diameter min. 4 mm, max. 10 mm, tightening torque 4 ± 0.6 Nm

3

Tightening torque 3.5 ± 0.5 Nm

4

Inlet ring with pressure tap (k-factor: 148)

5

Attachment holes for inlet ring and FlowGrid (00400-2-2957 not included in scope of delivery)

Item no. 54647-5-9970 · ENU · Change 212946 · Approved 2020-07-14 · Page 4 / 14

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3G355-PH49-02

Страница 1: ...permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the devic...

Страница 2: ...ore working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be ejected and caus...

Страница 3: ...Chapter 3 2 Nominal data Operating the device with all protective devices Following the operating instructions Improper use In particular operating the device in the following ways is prohibited and c...

Страница 4: ...r on top on request 2 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 3 Tightening torque 3 5 0 5 Nm 4 Inlet ring with pressure tap k factor 148 5 Attachment holes for inlet ring and Flow...

Страница 5: ...s determined using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 24 9 kg Size 355 mm Motor size 112 Rotor surface Painted black Electronics housing...

Страница 6: ...owner of the device to ensure if necessary after consultation with the network operator that this device is only connected to a connection point with a Ssc value that is greater than or equal to 120...

Страница 7: ...ustomer end of the cable can damage the device Make sure the end of the cable is connected in a dry environment Only connect the device to circuits that can be switched off with an all pole disconnect...

Страница 8: ...multiple of the nominal value 4 2 6 Locked rotor protection Due to the locked rotor protection the starting current LRA is equal to or less than the nominal current FLA 4 3 Connection in terminal box...

Страница 9: ...ible a drip edge can be produced by fitting a cable tie directly in front of the cable gland for example 4 4 Factory settings Factory settings made for the device by ebm papst Mode parameter set 1 PWM...

Страница 10: ...nics enable pin open or applied voltage 5 50 VDC disable bridge to GND or applied voltage 1 VDC reset function triggers software reset after a level change to 1 VDC SELV KL 3 8 Din2 Digital input 2 Sw...

Страница 11: ...ng Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with excessively high vibration levels can lead to premature failure The maximum per...

Страница 12: ...eck line voltage restore power supply Attention The error message resets automatically Device restarts automatically without warning Faulty connection Isolate from supply correct connection see connec...

Страница 13: ...pt the maintenance intervals to the actual level of dust exposure 6 3 Safety inspection NOTE High voltage test The integrated EMC filter has Y capacitors The tripping current is exceeded when AC testi...

Страница 14: ...tallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminum Non ferrous metal e g motor windings Plasti...

Отзывы: