Operating instructions

K3G355-AY40-35

Translation of the original operating instructions

4.5 Connection diagram

No.

Conn.

Designation

Function/assignment

KL 1

1

L1

Supply connection, power supply 3-phase 380-480 VAC, 50/60 Hz

KL 1

2

L2

Supply connection, power supply 3-phase 380-480 VAC, 50/60 Hz

KL 1

3

L3

Supply connection, power supply 3-phase 380-480 VAC, 50/60 Hz

PE

PE

Ground connection, PE connection

KL 2

1

NO

Status relay, floating status contact; make for failure

KL2

2

COM

Status relay, floating status contact; changeover contact; common connection; contact rating 250 VAC / max.
2 A (AC1) / min. 10 mA

KL2

3

NC

Status relay, floating status contact; break for failure

KL 3

1

RSA

Bus connection RS485, RSA, MODBUS-RTU; SELV

KL 3

2

RSB

Bus connection RS485, RSB, MODBUS-RTU; SELV

KL 3

3 / 10

GND

Reference ground for control interface; SELV

KL 3

4

Ain1 U

Analog input 1, set value: 0-10 V, Ri = 100 kΩ, adjustable curve, only usable as alternative to input Ain1 I;
SELV

KL 3

5

+ 10 V

Fixed voltage output 10 VDC, +10 V ±3%, max. 10 mA, short-circuit-proof power supply for external devices
(e.g. pot); SELV

KL 3

6

Ain1 I

Analog input 1, set value: 4-20 mA, Ri = 100 Ω, adjustable curve, only usable as alternative to input Ain1U;
SELV

KL 3

7

Din1

Digital input 1: enable electronics,
enable: pin open or applied voltage 5-50 VDC
disable: bridge to GND or applied voltage < 1 VDC
reset function: triggers software reset after a level change to < 1 VDC; SELV

KL 3

8

Din2

Digital input 2: Switching parameter sets 1/2, according to EEPROM setting, the valid or used parameter set
can be selected via bus or via digital input DIN2.
Parameter set 1: pin open or applied voltage 5-50 VDC
Parameter set 2: bridge to GND or applied voltage < 1 VDC; SELV

KL 3

9

Din3

Digital input 3: according to EEPROM setting, the integrated controller's direction of action can be selected as
normal/inverse via bus or digital input
normal: pin open or applied voltage 5-50 VDC
inverse: bridge to GND or applied voltage < 1 VDC; SELV

KL 3

11

Ain2 U

Analog input 2, measured value: 0-10 V, Ri = 100 kΩ, adjustable curve, only usable as alternative to input
Ain2I; SELV

KL 3

12

+ 20 V

Fixed voltage output 20 VDC, +20 V +25/-10%, max. 50 mA, short-circuit-proof power supply for external
devices (e.g. sensors); SELV

KL 3

13

Ain2 I

Analog input 2, measured value: 4-20 mA, Ri = 100 Ω, adjustable curve, only usable as alternative to input
Ain2U; SELV

KL 3

14

Aout

Analog output 0-10 VDC, max. 5 mA, output of current motor modulation level / motor speed
adjustable curve; SELV

Item no. 51322-5-9970 · ENU · Change 212946 · Approved 2020-07-14 · Page 10 / 14

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3G355-AY40-35

Страница 1: ...permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the devic...

Страница 2: ...ore working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be ejected and caus...

Страница 3: ...Chapter 3 2 Nominal data Operating the device with all protective devices Following the operating instructions Improper use In particular operating the device in the following ways is prohibited and c...

Страница 4: ...rtically as illustrated or rotor on bottom rotor on top on request 2 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 3 Inlet ring with pressure tap k factor 148 4 Tightening torque 3 5 0...

Страница 5: ...ng a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 22 8 kg Size 355 mm Motor size 112 Rotor surface Painted black Electronics housing material Die cas...

Страница 6: ...consultation with the network operator that this device is only connected to a connection point with a Ssc value that is greater than or equal to 120 times the rated output of the arrangement 4 CONNE...

Страница 7: ...ustomer end of the cable can damage the device Make sure the end of the cable is connected in a dry environment Only connect the device to circuits that can be switched off with an all pole disconnect...

Страница 8: ...multiple of the nominal value 4 2 6 Locked rotor protection Due to the locked rotor protection the starting current LRA is equal to or less than the nominal current FLA 4 3 Connection in terminal box...

Страница 9: ...ible a drip edge can be produced by fitting a cable tie directly in front of the cable gland for example 4 4 Factory settings Factory settings made for the device by ebm papst Mode parameter set 1 PWM...

Страница 10: ...nics enable pin open or applied voltage 5 50 VDC disable bridge to GND or applied voltage 1 VDC reset function triggers software reset after a level change to 1 VDC SELV KL 3 8 Din2 Digital input 2 Sw...

Страница 11: ...ng Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with excessively high vibration levels can lead to premature failure The maximum per...

Страница 12: ...eck line voltage restore power supply Attention The error message resets automatically Device restarts automatically without warning Faulty connection Isolate from supply correct connection see connec...

Страница 13: ...pt the maintenance intervals to the actual level of dust exposure 6 3 Safety inspection NOTE High voltage test The integrated EMC filter has Y capacitors The tripping current is exceeded when AC testi...

Страница 14: ...tallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminum Non ferrous metal e g motor windings Plasti...

Отзывы: