ebm-papst K3G355-AX56-02 Скачать руководство пользователя страница 5

Operating instructions

K3G355-AX56-02

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G112-EA

Phase

3~

Nominal voltage / VAC

400

Nominal voltage
range / VAC

380 .. 480

Frequency / Hz

50/60

Type of data definition

ml

Speed / min

-1

2140

Power input / W

1000

Current draw / A

1.65

Min. ambient temperature
/ °C

-25

Max. ambient
temperature
/ °C

50

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Data according to ErP directive

Installation category

A

Efficiency category

Static

Variable speed drive

Yes

Specific ratio

*

1.01

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Actual

Request
2013

Request
2015

Overall efficiency η

es

/ %

65.5

47.3

51.3

Efficiency grade N

76.2

58

62

Power input P

ed

/ kW

0.95

Air flow q

v

/ m³/h

3905

Pressure increase total p

sf

/ Pa

530

Speed n / min

-1

2150

Data definition with optimum efficiency.

The ErP data is determined using a motor-impeller combination in a standardised

measurement configuration.

3.4 Technical features

Mass

17.4 kg

Size

355 mm

Surface of rotor

Coated in black

Material of electronics
housing

Die-cast aluminium

Material of impeller

Aluminium sheet

Material of mounting
plate

Sheet steel, galvanised

Material of support
bracket

Steel, coated in black

Material of inlet nozzle

Sheet steel, galvanised

Number of blades

7

Direction of rotation

Clockwise, seen on rotor

Type of protection

IP 54

Insulation class

"B"

Humidity class

F4-1

Mounting position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensate discharge
holes

Rotor-side

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA
- Output for slave 0-10 V
- Input for sensor 0-10 V or 4-20 mA
- Alarm relay
- Integrated PID controller
- Motor current limit
- PFC, passive
- RS485 ebmBUS
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Over-temperature protected
electronics / motor
- Line undervoltage / phase failure
detection

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical leads

Via terminal box

Motor protection

Thermal overload protector (TOP) wired
internally

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 61800-5-1; CE

Approval

CCC; CSA C22.2 Nr.77; EAC; UL
1004-3

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.5 Mounting data

;

Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

3.6 Transport and storage conditions

;

Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+80 °C

Min. permissible
ambient motor temp.
(transp./storage)

-40 °C

Item no. 50642-5-9970 · ENG · Revision 82542 · Release 2015-01-05 · Page 5 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3G355-AX56-02

Страница 1: ...tted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must b...

Страница 2: ...otor and impeller can be injured Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill DANGER Flying parts Missing safety dev...

Страница 3: ...ce in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustain...

Страница 4: ...shown in the view or rotor on bottom rotor on top on request 2 Cable diameter min 4 mm max 10 mm tightening torque 2 5 0 4 Nm 3 Inlet nozzle with bleeder connection for pressure relief k factor 148 4...

Страница 5: ...bottom rotor on top on request Condensate discharge holes Rotor side Operation mode S1 Motor bearing Ball bearing Technical features Output 10 VDC max 10 mA Output 20 VDC max 50 mA Output for slave 0...

Страница 6: ...vices must no longer be installed Install the undamaged device according to your application 4 2 Connecting the electrical system DANGER Electric voltage on the device Electric shock Always install a...

Страница 7: ...motor is at a standstill and the mains voltage is switched on The values lie in a range of typical 250 mA The effective power in this operating state readiness for operation is simultaneously at typic...

Страница 8: ...d at the bottom The cables must always be routed downwards Fig 3 Cable routing for fans installed upright 4 4 Factory settings Factory settings with which the device is pre set by ebm papst Operation...

Страница 9: ...ent 10 V equate to 100 level control coefficient KL3 2 8 GND Reference mass for control interface SELV KL3 3 7 0 10 V Use control actual value input 0 10 VDC impedance 100 k only as alternative to 4 2...

Страница 10: ...move any that are found Apply the nominal voltage to the voltage supply Start the device by changing the input signal 4 8 Switching off the device Switching off the device during operation Switch off...

Страница 11: ...al blockage Mains supply voltage faulty Check mains supply voltage restore power supply Important The error message resets automatically The device starts up again automatically without advance warnin...

Страница 12: ...e protective casing against accidental contact for damage and to ensure that it is intact Visual inspection At least every 6 months Repair or replacement of the device Check the device for damage to b...