Operating instructions

K3G355-AI56-01

Translation of the original operating instructions

If you have any other problems, contact ebm-papst.

6.1 Cleaning

NOTE
Damage to the device during cleaning.

Malfunction possible
→ Do not clean the device using a water jet or high-pressure

washer.

→ Do not use any cleaners containing acids,

bases or solvents.

→ Do not use any pointed or sharp-edged objects to clean.

6.2 Safety test

NOTE
High-voltage test

The integrated EMC filter contains Y capacitors. Therefore, the
trigger current is exceeded when AC testing voltage is applied.
→ Test the device with DC voltage when you carry out the

high-voltage test required by law. The voltage to be used
corresponds to the peak value of the AC voltage required by
the standard.

What has to
be tested?

How to test?

Frequency

Which
measure?

Check the
protective
casing against
accidental
contact for
damage and to
ensure that it is
intact

Visual inspection At least every

6 months

Repair or
replacement of
the device

Check the
device for
damage to
blades and
housing

Visual inspection At least every

6 months

Replacement
of the device

Mounting the
connection lines

Visual inspection At least every

6 months

Fasten

Check the
insulation of
the wires for
damage

Visual inspection At least every

6 months

Replace wires

Impeller for
wear/deposits/
corrosion and
damage

Visual inspection At least every

6 months

Clean or
replace impeller

Tightness of
screwed cable
gland

Visual inspection At least every

6 months

Retighten,
replace if
damaged

Condensate
discharge
holes for
clogging, as
necessary

Visual inspection At least every

6 months

Open bore holes

Item no. 52325-5-9970 · Revision 82547 · Release 2014-05-08 · Page 12 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3G355-AI56-01

Страница 1: ...mitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must...

Страница 2: ...rotor and impeller can be injured Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill DANGER Flying parts Missing safety d...

Страница 3: ...se hazards Operating the device with an imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustaining or lifesaving function Operation with external vibrations M...

Страница 4: ...measures have the unit mm 1 Cable diameter min 4 mm max 10 mm tightening torque 2 5 0 4 Nm 2 Tightening torque 3 5 0 5 Nm Item no 52325 5 9970 Revision 82547 Release 2014 05 08 Page 4 12 ebm papst Mu...

Страница 5: ...tion Shaft horizontal or rotor on bottom rotor on top on request Operation mode S1 Motor bearing Ball bearing Technical features Output 10 VDC max 10 mA Output 20 VDC max 50 mA Output for slave 0 10 V...

Страница 6: ...devices must no longer be installed Install the undamaged device according to your application 4 2 Connecting the electrical system DANGER Electric voltage on the device Electric shock Always install...

Страница 7: ...e motor is at a standstill and the mains voltage is switched on The values lie in a range of typical 250 mA The effective power in this operating state readiness for operation is simultaneously at typ...

Страница 8: ...ged at the bottom The cables must always be routed downwards Fig 3 Cable routing for fans installed upright 4 4 Factory settings Factory settings with which the device is pre set by ebm papst Operatio...

Страница 9: ...cient 10 V equate to 100 level control coefficient KL3 2 8 GND Reference mass for control interface SELV KL3 3 7 0 10 V Use control actual value input 0 10 VDC impedance 100 k only as alternative to 4...

Страница 10: ...remove any that are found Apply the nominal voltage to the voltage supply Start the device by changing the input signal 4 8 Switching off the device Switching off the device during operation Switch of...

Страница 11: ...ical blockage Mains supply voltage faulty Check mains supply voltage restore power supply Important The error message resets automatically The device starts up again automatically without advance warn...

Страница 12: ...the protective casing against accidental contact for damage and to ensure that it is intact Visual inspection At least every 6 months Repair or replacement of the device Check the device for damage to...

Отзывы: