Operating instructions

K3G310-PV69-03

Translation of the original operating instructions

;

Even devices explicitly intended for outdoor use are to be stored as
described prior to commissioning.

;

Maintain the storage temperature, see
Chapter 3.6 Transport and storage conditions.

;

Make sure that all cable glands are fitted with dummy plugs.

2. INTENDED USE

The device is exclusively designed as a built-in device for conveying
air according to its technical data.
Any other usage above and beyond this does not conform with the
intended purpose and constitutes misuse of the device.
Customer equipment must be capable of withstanding the mechanical
and thermal stresses that can arise from this product. This applies for the
entire service life of the equipment in which this product is installed.

Intended use also includes

The device is only to be used in power systems with grounded
neutral (TN/TT power systems), in power systems with phase
conductor grounding, or in IT power systems.

The device is to be used in networks with network quality
characteristics as per EN 50160.

Using the device only in stationary systems.

Performing all maintenance work.

Conveying air at an ambient air pressure between 800 mbar and
1050 mbar.

Using the device within the permitted ambient temperature range; see
Chapter 3.6 Transport and storage conditions and
Chapter 3.2 Nominal data.

Operating the device with all protective devices.

Following the operating instructions.

Improper use

In particular, operating the device in the following ways is prohibited and
could be hazardous:

Operating the device in an unbalanced state, e.g. due to dirt deposits
or ice formation.

Resonant operation, operation with severe vibration. This also
includes vibration transmitted to the fan from the customer installation.

Operation in medical equipment with a life-sustaining or life-support
function.

Conveying solids in the flow medium.

Painting the device

Connections (e.g. screws) coming loose during operation.

Opening the terminal box during operation.

Conveying air that contains abrasive particles.

Conveying highly corrosive air, e.g. salt spray. Exception: devices
designed for salt spray and correspondingly protected.

Conveying air with high dust content, e.g. suctioning off sawdust.

Operating the device close to flammable materials or components.

Operating the device in an explosive atmosphere.

Using the device as a safety component or to perform safety-related
functions.

Operation with completely or partially disassembled or manipulated
protective devices.

In addition, all applications not listed among the intended uses.

Item no. 57280-5-9970 · ENU · Change 218409 · Approved 2020-09-10 · Page 3 / 17

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3G310-PV69-03

Страница 1: ...a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installatio...

Страница 2: ...ore working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be ejected and caus...

Страница 3: ...6 Transport and storage conditions and Chapter 3 2 Nominal data Operating the device with all protective devices Following the operating instructions Improper use In particular operating the device i...

Страница 4: ...htening torque 4 0 6 Nm The tightening torque is designed for PVC cables If the cable materials are different the tightening torque may have to be adjusted 3 Tightening torque 1 5 0 2 Nm 4 Inlet ring...

Страница 5: ...m papst evaluation loses its validity the conformity must be confirmed again The product does not fall within the scope of Regulation EU 2019 1781 due to the exception specified in Article 2 2a motors...

Страница 6: ...the responsibility of the installation engineer or operator owner of the device to ensure if necessary after consultation with the network operator that this device is only connected to a connection...

Страница 7: ...ustomer end of the cable can damage the device Make sure the end of the cable is connected in a dry environment Only connect the device to circuits that can be switched off with an all pole disconnect...

Страница 8: ...the starting current LRA is equal to or less than the nominal current FLA 4 3 Connection in terminal box 4 3 1 Preparing cables for connection Only strip the cable as far as necessary ensuring that t...

Страница 9: ...e 3 5 0 4 Nm Connect the cables to the corresponding terminals Use a screwdriver to do so When connecting make sure the wires do not splay out Insert the strands until they meet with resistance Fig 5...

Страница 10: ...eristic curve P1 IN SELV CON2 IO3 Function parameterizable see Optional interface functions table Factory setting Analog output 0 10 V max 5 mA function Fan modulation level Characteristic curve param...

Страница 11: ...159 0 Ain2 0 10V PWM analog input D159 2 Ri 100K characteristic curve parameterizable f PWM 1k 10KHz SELV Ain2 4 20mA analog input Ri 125R characteristic curve parameterizable SELV D159 3 Din3 active...

Страница 12: ...operating instructions 4 7 Equivalent circuit diagrams Item no 57280 5 9970 ENU Change 218409 Approved 2020 09 10 Page 12 17 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 49 0 793...

Страница 13: ...ng Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with excessively high vibration levels can lead to premature failure The maximum per...

Страница 14: ...atically Device restarts automatically without warning Faulty connection Isolate from supply correct connection see connection diagram Broken motor winding Replace device Deficient cooling Improve coo...

Страница 15: ...perating point Reduce ambient temperature Correct operating point Manual reset required 7 Hall sensor error Internal error Switch off line voltage wait switch back on 8 Motor blocked Mechanical blocka...

Страница 16: ...eller or replace device Tightness of cable gland Visual inspection At least every 6 months Retighten replace if damaged Condensation drainage holes for clogging where necessary Visual inspection At le...

Страница 17: ...aterials and are therefore to be treated in the same manner The materials concerned are as follows Miscellaneous insulators used in the terminal box Power cables Cables for internal wiring Electrolyti...