ebm-papst K3G310-AX52-05 Скачать руководство пользователя страница 11

Operating instructions

K3G310-AX52-05

Translation of the original operating instructions

If you have any other problems, contact ebm-papst.

6.1 Cleaning

NOTE
Damage to the device during cleaning.

Malfunction possible
→ Do not clean the device using a water jet or high-pressure

washer.

→ Do not use any cleaners containing acids,

bases or solvents.

→ Do not use any pointed or sharp-edged objects to clean.

6.2 Safety test

NOTE
High-voltage test

The integrated EMC filter contains Y capacitors. Therefore, the
trigger current is exceeded when AC testing voltage is applied.
→ Test the device with DC voltage when you carry out the

high-voltage test required by law. The voltage to be used
corresponds to the peak value of the AC voltage required by
the standard.

What has to
be tested?

How to test?

Frequency

Which
measure?

Check the
protective
casing against
accidental
contact for
damage and to
ensure that it is
intact

Visual inspection At least every

6 months

Repair or
replacement of
the device

Check the
device for
damage to
blades and
housing

Visual inspection At least every

6 months

Replacement
of the device

Mounting the
connection lines

Visual inspection At least every

6 months

Fasten

Mounting of
protective
earth connection

Visual inspection At least every

6 months

Fasten

Check the
insulation of
the wires for
damage

Visual inspection At least every

6 months

Replace wires

Impeller for
wear/deposits/
corrosion and
damage

Visual inspection At least every

6 months

Clean or
replace impeller

Condensate
discharge
holes for
clogging, as
necessary

Visual inspection At least every

6 months

Open bore holes

Check the ball
bearings to
ensure they
are quiet, can
move easily
and are free of
play

Manual check
by turning the
rotor in shut-off
state

At least every
6 months

Replace
device in case
of noise,
difficulty of
movement or
clearance of
the bearings

Item no. 50749-5-9970 · Revision 70943 · Release 2011-12-06 · Page 11 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3G310-AX52-05

Страница 1: ...permitted to transport unpack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must...

Страница 2: ...parts that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstil...

Страница 3: ...ng the device with an imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustaining or lifesaving function Operation with external vibrations Moving solids conte...

Страница 4: ...3 L2 black 2 2 4 L1 black 1 3 Connection line AWG 18 and AWG 22 with connector housing Phoenix order no 17 57 05 1 3 1 10V red 3 2 GND blue 3 3 0 10V PWM yellow 3 4 Not defined orange 3 5 NC alarm wh...

Страница 5: ...les Rotor side Operation mode S1 Motor bearing Ball bearing Technical features Output 10 VDC max 10 mA Tach output Alarm relay Integrated PID controller Motor current limit PFC passive RS485 ebmBUS So...

Страница 6: ...cting the electrical system DANGER Electric voltage on the device Electric shock Always install a protective earth first Check the protective earth DANGER Incorrect insulation Risk of fatal injury fro...

Страница 7: ...ed for compliance with EMC limits interference emission and interference immunity idle currents in the mains cable can be measured even when the motor is at a standstill and the mains voltage is switc...

Страница 8: ...10 mA AC1 1 7 NC white 2 Floating status message contact break for failure 2 8 0 10 V yellow Control input set value 0 10 VDC impedance 100 kOhm SELV 2 11 10 V red Voltage output 10 VDC 3 max 10 mA s...

Страница 9: ...eration on and off via power supply Switching off the device for maintenance work Switch on the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply...

Страница 10: ...ical blockage Mains supply voltage faulty Check mains supply voltage restore power supply Important The error message resets automatically The device starts up again automatically without advance warn...

Страница 11: ...ast every 6 months Repair or replacement of the device Check the device for damage to blades and housing Visual inspection At least every 6 months Replacement of the device Mounting the connection lin...