background image

Operating instructions

K3G280-BC01-N1

Translation of the original operating instructions

3.1.1 Mounting dimensions

All dimensions in mm.

Item no. 56761-5-9970 · ENU · Change 257059 · Approved 2023-02-03 · Page 5 / 14

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3G280-BC01-N1

Страница 1: ...by suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation...

Страница 2: ...ible radiation levels occur following installation appropriate shielding measures have to be taken by the user NOTE Electrical or electromagnetic interference after installing the device in customer e...

Страница 3: ...an ambient air pressure between 800 mbar and 1050 mbar Using the device within the permitted ambient temperature range see Chapter 3 5 Transport and storage conditions and Chapter 3 2 Nominal data Op...

Страница 4: ...gen free railway application EN 45545 4G 1 5 mm 4x wire end ferrule 2 Cable halogen free railway application EN 45545 7x 0 5 mm 7x wire end ferrule Item no 56761 5 9970 ENU Change 257059 Approved 2023...

Страница 5: ...ng instructions 3 1 1 Mounting dimensions All dimensions in mm Item no 56761 5 9970 ENU Change 257059 Approved 2023 02 03 Page 5 14 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 4...

Страница 6: ...3 5 mA Motor protection Thermal overload protector TOP internally connected with cable Lateral Protection class I with customer connection of protective earth Conformity with standards EN 15085 1 CPC3...

Страница 7: ...ical injury such as back injuries Two people should work together to remove the device from its packaging NOTE Damage to the device from vibration Bearing damage shorter service life The fan must not...

Страница 8: ...380 480 VAC 16 A 15 A C16A 1 5 16 3 PE AC 380 480 VAC 20 A 20 A C20A 2 5 14 3 PE AC 380 480 VAC 25 A 25 A C25A 4 0 12 AWG American Wire Gauge 4 2 3 Reactive currents Because of the EMC filter integrat...

Страница 9: ...instructions Direction of action parameter set 2 Positive heating Item no 56761 5 9970 ENU Change 257059 Approved 2023 02 03 Page 9 14 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phon...

Страница 10: ...NC orange Status relay floating status contact break for failure contact rating 250 VAC max 2 A AC1 min 1 mA 5 VDC reinforced insulation on control interface side basic insulation on supply side acco...

Страница 11: ...issible vibration severity must not exceed 3 5 mm s and should be checked at intervals of 6 months It is to be determined at the motor mount at the motor support plate at least in axial direction and...

Страница 12: ...y Device restarts automatically without warning Faulty connection Isolate from supply correct connection see connection diagram Broken motor winding Replace device Thermal overload protector activated...

Страница 13: ...er for wear deposits corrosion and damage Visual inspection At least every 6 months Clean impeller or replace device Condensation drainage holes for clogging where necessary Visual inspection At least...

Страница 14: ...aterials and are therefore to be treated in the same manner The materials concerned are as follows Miscellaneous insulators used in the terminal box Power cables Cables for internal wiring Electrolyti...

Отзывы: