3.2 Nominal data

Motor

M3G084-FA

Phase

1~

Nominal voltage / VAC

230

Nominal voltage
range / VAC

200 .. 277

Frequency / Hz

50/60

Method of obtaining
data

ml

Speed (rpm) / min

-1

2400

Power consumption / W

415

Current draw / A

2.7

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

40

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Data according to Commission Regulation (EU) 327/
2011

Actual

Req. 2015

01 Overall efficiency η

es

/ %

61.3

47.8

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

75.5

62

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
product's rating label.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart
· HRA 590344
D-74673 Mulfingen

08 Type

K3G280-AT04-74

09 Power consumption P

ed

/ kW

0.44

09 Air flow q

v

/ m³/h

1755

09 Pressure increase total p

sf

/

Pa

502

10 Speed (rpm) n / min

-1

2340

11 Specific ratio

*

1.01

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data obtained at optimum efficiency level. The ErP data is determined using a motor-impeller

combination in a standardized measurement setup.

3.4 Technical description

Weight

9.9 kg

Size

280 mm

Motor size

84

Rotor surface

Painted black

Electronics housing
material

Die-cast aluminum, painted black

Impeller material

Sheet aluminum, painted black

Support plate material

Sheet steel, galvanized and painted black

Support bracket
material

Steel, painted black

Inlet nozzle material

Sheet steel, painted black

Number of blades

7

Direction of rotation

Clockwise, viewed toward rotor

Degree of protection

IP54

Insulation class

"B"

Moisture (F) /
Environmental (H)
protection class

H2+S

Installation position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensation
drainage holes

On rotor side

Mode

S1

Motor bearing

Ball bearing

Technical features

- Control input 0-10 VDC / PWM
- Output 10 VDC, max. 1.1 mA
- Thermal overload protection for
electronics/motor
- Alarm relay
- Line undervoltage detection
- Motor current limitation
- Soft start

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Motor protection

Thermal overload protector (TOP)
internally connected

with cable

Variable

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 61800-5-1; CE

Approval

CCC

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

;

Use the device in accordance with its degree of protection.

Item no. 50588-5-9970 · ENU · Change 211092 · Approved 2020-05-20 · Page 5 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3G280-AT04-74

Страница 1: ...d specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associat...

Страница 2: ...g on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become entangled and be pulled into the...

Страница 3: ...ting the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with sever...

Страница 4: ...All dimensions in mm 1 Pressure tap k factor 93 2 Cable AWG18 5x crimped ferrules 3 Cable AWG22 3x crimped ferrules Item no 50588 5 9970 ENU Change 211092 Approved 2020 05 20 Page 4 11 ebm papst Mulfi...

Страница 5: ...P data is determined using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 9 9 kg Size 280 mm Motor size 84 Rotor surface Painted black Electronics ho...

Страница 6: ...ng by grasping hold of the frame Never subject to any impact Wear safety shoes and cut resistant safety gloves NOTE Damage to the device from vibration Bearing damage shorter service life The fan must...

Страница 7: ...or the protective earth connection circuit must be verified in the end application Depending on the installation situation it may be necessary to connect an additional protective earth conductor by wa...

Страница 8: ...ting instructions 4 4 Connection diagram Drawing preliminary Item no 50588 5 9970 ENU Change 211092 Approved 2020 05 20 Page 8 11 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 49...

Страница 9: ...e during operation Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Switching off the device for maintenance Switch off the devic...

Страница 10: ...ice life check the fans regularly for proper operation and soiling The frequency of checking is to be adapted accordingly depending on the degree of soiling DANGER Risk of injury from rotating fan Onl...

Страница 11: ...or ecological disposal of the product and its components 6 4 1 Country specific legal requirements NOTE Country specific legal requirements Always observe the applicable country specific legal regulat...

Отзывы: