Operating instructions

K3G225-RD05-03

Translation of the original operating instructions

(RCCB) with a trip threshold of 300 mA and delayed tripping
(super-resistant, characteristic K).

4.2.4 Locked-rotor protection

Due to the locked-rotor protection, the starting current (LRA) is
equal to or less than the nominal current (FLA).

4.3 Connecting the cables

The device has external leads.

;

First connect the "PE" (protective earth).

Connect the cables according to your application. When doing so,
observe Chapter 4.4 Connection diagram.

Item no. 51019-5-9970 · ENU · Change 96553 · Approved 2017-10-26 · Page 7 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3G225-RD05-03

Страница 1: ...lified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safet...

Страница 2: ...Electrical or electromagnetic interference after installing the device in customer equipment Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury...

Страница 3: ...ons Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Res...

Страница 4: ...dimensions in mm 1 Cable PVC 3G AWG20 3x crimped splices 2 Cable PVC 4x AWG22 4x crimped splices 3 Mounting dimensions Item no 51019 5 9970 ENU Change 96553 Approved 2017 10 26 Page 4 11 ebm papst Mu...

Страница 5: ...ve earth Conformity with standards EN 60335 1 CE Approval CCC C22 2 No 77 CAN CSA E60730 1 UL 1004 7 60730 EAC With regard to cyclic speed loads note that the rotating parts of the device are designed...

Страница 6: ...prevent it from being switched back on NOTE Water ingress into wires or cables Water ingress at the customer end of the cable can damage the device Make sure the end of the cable is connected in a dry...

Страница 7: ...ent LRA is equal to or less than the nominal current FLA 4 3 Connecting the cables The device has external leads First connect the PE protective earth Connect the cables according to your application...

Страница 8: ...ve earth 1 GND blue GND connection for control interface 2 0 10V PWM yellow Control input 0 10 V or PWM electrically isolated 3 10 V max 1 1 mA red Voltage output 10 VDC 1 1 mA electrically isolated s...

Страница 9: ...e g in cyclic operation on and off via power supply Disconnect the device from the power supply When disconnecting be sure to disconnect the ground connection last 5 INTEGRATED PROTECTIVE FEATURES The...

Страница 10: ...rigorously implemented around the world on the basis of German standards Right from the development stage ecological design technical safety and health protection are fixed criteria The following sec...

Страница 11: ...mploying the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 51019 5 9970 ENU Change 96553 Approved 2017 10 26 Page 11 11 ebm papst Mulfinge...

Отзывы: