ebm-papst K3G146-AD01-01 Скачать руководство пользователя страница 8

Operating instructions

K3G146-AD01-01

Translation of the original operating instructions

4.4 Connection diagram

Drawing preliminary!

No.

Conn.

Designation

Color

Function/assignment

CON10

10.1

PE

green/
yellow

Protective earth

CON10

10.2

L

black

Power supply 230 VAC, 50-60 Hz, see nameplate for voltage range

CON10

10.3

N

blue

Neutral conductor

CON11

11.1

10 V/max. 1.1
mA

red

Voltage output 10 V, 1.1 mA, electrically isolated, not short-circuit-proof

CON11

11.2

Tach

white

Tach output: Open collector, 1 pulse per revolution, electrically isolated, Isink max = 10 mA

CON11

11.3

0-10 V PWM

yellow

Control input 0-10 V or PWM, electrically isolated

CON11

11.4

GND

blue

GND connection for control interface

Item no. 51517-5-9970 · ENU · Change 260701 · Approved 2022-07-01 · Page 8 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3G146-AD01-01

Страница 1: ...f Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety...

Страница 2: ...y that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accide...

Страница 3: ...prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration...

Страница 4: ...h 1 3 0 10 V lin PWM 1 4 GND 2 Connector Lumberg 3642 03 K01 pluggable with 3626 03 K01 2 1 PE 2 2 L 2 3 N 3 8x sheet metal nut for thread EN ISO 1478 ST4 8 min screw length 14 5 mm plus material thic...

Страница 5: ...1 due to the exception specified in Article 2 2a motors completely integrated into a product 3 4 Technical description Weight 4 2 kg Size 146 mm Motor size 74 Rotor surface Galvanized Electronics hous...

Страница 6: ...free attachment of the fan to the substructure The fan may not be handled in the area around the inlet nozzle during transport and installation There is a risk of damage to the impeller Check the devi...

Страница 7: ...th conductor by way of the extra protective earth terminal provided on the device 4 2 2 Reactive currents Because of the EMC filter integrated for compliance with EMC limits interference emission and...

Страница 8: ...10 V max 1 1 mA red Voltage output 10 V 1 1 mA electrically isolated not short circuit proof CON11 11 2 Tach white Tach output Open collector 1 pulse per revolution electrically isolated Isink max 10...

Страница 9: ...the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the power supply When disconnecting be sure to disconnect the g...

Страница 10: ...ent is necessary after that period contact ebm papst Adapt the maintenance intervals to the actual level of dust exposure 6 2 Safety inspection NOTE High voltage test The integrated EMC filter has Y c...

Страница 11: ...num Non ferrous metal e g motor windings Plastics particularly with brominated flame retardants in accordance with marking Insulating materials Cables and wires Electronic scrap e g circuit boards Onl...

Отзывы: