Operating instructions

K3G097-AS82-82

Translation of the original operating instructions

3.5 Mounting data

Strength class for
mounting screws

8.8

;

Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).

For depth of screw, see chapter 3.1 Product drawing
Any further mounting data required can be taken from the product
drawing or Section chapter 4.1 Connecting the mechanical system.

3.6 Transport and storage conditions

Max. permissible
ambient motor temp.
(transp./ storage)

+85 °C

Min. permissible
ambient motor temp.
(transp./storage)

-40 °C

3.7 Electromagnetic compatibility

EMC directives

according to EN 50121-3-2

4. CONNECTION AND START-UP

4.1 Connecting the mechanical system

CAUTION
Cutting and crushing hazard when removing device
from packaging

→ Carefully remove the device from its packaging, only

touching the housing. Strictly avoid shocks.

→ Wear safety shoes and cut-resistant safety gloves.

NOTE
Damage to device from vibration

Bearing damage, reduced service life
→ Forces or impermissibly high vibration levels must not be

transmitted to the fan from system components.

→ If the fan is connected to air ducts, it should isolated from

vibrations, for example using compensators or similar
elements.

→ Fasten the fan to the substructure without distorting it.

;

The fan may not be handled in the area around the inlet nozzle during
transport and installation.
There is a risk of damage to the impeller.

;

Check the device for transport damage. Damaged devices must no
longer be installed.

;

Install the undamaged device according to your application.

CAUTION
Possibility of damage to the device

Serious damage may result if the device slips during assembly.
→ Keep the device fixed in position at the installation location

until all attachment screws have been tightened.

The fan must not be strained on fastening.

4.2 Connecting the electrical system

CAUTION
Electrical voltage

The fan is a built-in component and features no electrically
isolating switch.
→ Only connect the fan to circuits that can be switched off with

an all-pole separating switch.

→ When working on the fan, you must switch off the

installation/machine in which the fan is installed and secure it
from being switched on again.

NOTE
Water penetration into leads or wires

Water enters at the cable end on the customers side and can
damage the device.
→ Make sure that the cable end is connected in a dry

environment.

Operate the device with a safely isolated power pack.

4.2.1 Prerequisites

;

Check that the data on the type plate match the connection data.

;

Before connecting the device, ensure that the supply voltage matches
the operating voltage of the device.

;

Only use cables designed for current according to the type plate.
For determining the cross-section, follow the basic principles in
accordance with EN 61800-5-1. The protective earth must have a
cross-section equal to or greater than the outer conductor cross-
section.
We recommend the use of 105°C cables. Ensure that the minimum
cable cross-section is at least
AWG26/0.13 mm².

4.3 Connection of the cables

External leads are brought out of device.

Connect the lines according to your application. When doing so,
observe chapter 4.4 Connection screen.

Item no. 54108-5-9970 · ENG · Revision 213957 · Release 2020-07-14 · Page 6 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3G097-AS82-82

Страница 1: ...all the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluat...

Страница 2: ...evice against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair dangling items of clothing jewellery and similar...

Страница 3: ...lowing ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibrations These also inclu...

Страница 4: ...sures have the unit mm 1 Connection line halogen free railway application EN 45545 2x 6 0 mm 2x 1 0 mm 4x core end sleeve Item no 54108 5 9970 ENG Revision 213957 Release 2020 07 14 Page 4 10 ebm paps...

Страница 5: ...tor IP24 KM electronics IP6K9K mating connector fitted Insulation class B Humidity F environmental protection class H H3 Note ambient temperature Occasional start up between 40 C and 25 C is permissib...

Страница 6: ...e to the device Serious damage may result if the device slips during assembly Keep the device fixed in position at the installation location until all attachment screws have been tightened The fan mus...

Страница 7: ...3 DIAG white Diagnostic output Open collector Isink max 10 mA Ri 50 Fan OK High Fan error Low 4 INVLIN not used 5 0 10 V PWM yellow Control input Ri 47 k 0 10 V typ 1 V n 0 1 5 V n min 10 V n max PWM...

Страница 8: ...control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the supply voltage 5 MAINTENANCE MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not...

Страница 9: ...ontact for damage and to ensure that it is intact Visual inspection At least every 6 months Repair or replacement of the device Check the device for damage to blades and housing Visual inspection At l...

Страница 10: ...external rotor motors from ebm papst Mulfingen GmbH Co KG Ferrite magnets can be disposed of in the same way as normal iron and steel Electrical insulating materials on the product in cables and wires...

Отзывы: