Operating instructions
G3G200-GN20-01
Translation of the original operating instructions
4.3 Connection screen
No.
Pin
Signal
Function / assignment
ST1
1; 2; 3 L; N; PE
Power supply 230 VAC, 50 - 60 Hz, phase, neutral, protective earth
ST2
1
UB
External voltage 16 - 45 VDC, residual /- 3.5%, SELV
ST2
2
Tach
Speed monitoring, 3 pulses per revolution, SELV
ST2
3
0 - 10 V
Control input 0 - 10 V, impedance 100k, SELV
ST2
4
PWM
Control input PWM, 1 - 6 kHz, SELV
ST2
5
GND
GND - Connection for control interface, SELV
Item no. 50365-5-9970 · Revision 68161 · Release 2009-10-09 · Page 9 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com