![ebm-papst G3G160-AC70-01 Скачать руководство пользователя страница 8](http://html1.mh-extra.com/html/ebm-papst/g3g160-ac70-01/g3g160-ac70-01_operating-instructions-manual_4224596008.webp)
Operating instructions
G3G160-AC70-01
Translation of the original operating instructions
4.4 Connection diagram
Drawing preliminary!
Not switchable via power supply. Restart via input voltage only after 5 minute delay.
No.
Conn.
Designation
Color
Function/assignment
4
L
black
Supply connection, power supply, phase, voltage range see nameplate, 50/60 Hz
3
N
blue
Supply connection, power supply, neutral conductor, voltage range see nameplate, 50/60 Hz
1
PE
green/
yellow
Ground connection
8
0-10 V / PWM
yellow
0-10 V / PWM control input, Ri=100 kΩ, SELV
9
Tacho
white
Tach output, open collector, 1 pulse per revolution, Isink max = 10 mA, SELV
11
+10 V
red
Fixed voltage output 10 VDC +/-3 %, Imax.= 1.1 mA, short-circuit-proof, power supply for ext.
devices (e.g. potentiometers), SELV
12
GND
blue
Reference ground for control interface, SELV
Item no. 54129-5-9970 · ENU · Change 200166 · Approved 2019-06-17 · Page 8 / 11
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com